Plan Review Notes
Plan Review Notes For Permit 19070494
Permit Number 19070494
Review Stop M
Sequence Number 1
Notes
Date Text
2019-08-13 08:56:041ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19070494
 8/13/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.1.1: THE PLAN APPEARS TO SHOW AIR BEING
 RETURNED FROM THE TOILET ROOMS TO RTU-1 WHICH IS
 PROHIBITED- 601.5 FBC M.
 2) M1.1.1: THE 30X12 TRANSFER GRILL RETURNING AIR VIA
 THE CORRIDOR IS PROHIBITED PER SECTION 601.2 FBC M.
 3) A.1.2.1.: 42? HIGH GUARD RAILS SHALL BE INSTALLED
 ALONG THE ROOF EDGES BY THE NEW RTU?S UNLESS THERE IS
 AN EXISTING 42? HIGH PARAPET WALL- SEE SECTION 304.11
 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  