| 2019-07-15 12:43:10 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET LS 1.1 - THERE APPEARS TO BE A NEW 1-HOUR WALL |
| | IS INDICATED WITHIN THE CENTER AREA OF THE BUILDING; |
| | HOWEVER THERE IS AN OPEN AREA AT THE FRONT DESK AREA. |
| | |
| | THERE IS NO NET FIRE SEPARATION FOR THIS NEW 1 HOUR |
| | WALL AND I'M NOT SURE OF THE DESING ATTEMPT. |
| | |
| | IS THIS A MIXED, SEPARATED OR NONSEPARATED OCCUPANCY? |
| | |
| | PER NFPA 101, CH 6, OCCUPANCY CLSSIFICATION |
| | |
| | 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE |
| | IN WHICH TWO |
| | OR MORE CLASSES OF OCCUPANCY EXIST. |
| | 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE |
| | THE |
| | OCCUPANCIES ARE INTERMINGLED. |
| | 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY |
| | WHERE THE |
| | OCCUPANCIES ARE SEPARATED BY FIRE RESISTANCE?RATED |
| | ASSEMBLIES. |
| | 6.1.14.3 MIXED OCCUPANCIES. |
| | 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE |
| | CLASSIFIED AS TO ITS USE IN |
| | ACCORDANCE WITH SECTION 6.1. |
| | 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST |
| | RESTRICTIVE |
| | REQUIREMENTS OF THE OCCUPANCIES INVOLVED, UNLESS |
| | SEPARATE SAFEGUARDS |
| | ARE APPROVED. |
| | 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.) |
| | 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED, |
| | EACH PART OF THE |
| | BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED |
| | IN THIS CHAPTER, |
| | SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY |
| | FIRE-RESISTIVE |
| | ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3, |
| | TABLE 6.1.14.4.1(A), |
| | AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED |
| | BY APPROVED |
| | EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY |
| | 6.1.14.4.6. |
| | 6.1.14.4.2 OCCUPANCY SEPARATIONS SHALL BE CLASSIFIED AS |
| | 3-HOUR FIRE |
| | RESISTANCE?RATED, 2-HOUR FIRE RESISTANCE?RATED, OR |
| | 1-HOUR FIRE |
| | RESISTANCE?RATED AND SHALL MEET THE REQUIREMENTS OF |
| | CHAPTER 8. |
| | 6.1.14.4.3 THE MINIMUM FIRE RESISTANCE RATING SPECIFIED |
| | IN TABLE |
| | 6.1.14.4.1(A) AND TABLE 6.1.14.4.1(B) SHALL BE |
| | PERMITTED TO BE |
| | REDUCED BY 1 HOUR, BUT IN NO CASE SHALL IT BE REDUCED |
| | TO LESS THAN 1 |
| | HOUR, WHERE THE BUILDING IS PROTECTED THROUGHOUT BY AN |
| | APPROVED |
| | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH |
| | 9.7.1.1(1) AND |
| | SUPERVISED IN ACCORDANCE WITH 9.7.2, UNLESS PROHIBITED |
| | BY THE |
| | DOUBLE-DAGGER FOOTNOTE ENTRIES IN THE TABLES. |
| | 6.1.14.4.4 OCCUPANCY SEPARATIONS SHALL BE VERTICAL, |
| | HORIZONTAL, OR |
| | BOTH OR, WHEN NECESSARY, OF SUCH OTHER FORM AS REQUIRED |
| | TO PROVIDE |
| | COMPLETE SEPARATION BETWEEN OCCUPANCY DIVISIONS IN THE |
| | BUILDING. |
| | 6.1.14.4.5* EACH SEPARATED PORTION OF THE BUILDING |
| | SHALL COMPLY |
| | WITH THE REQUIREMENTS FOR THE OCCUPANCY THEREIN. |
| | |
| | PLEASE CLARIFY AND CORRECT ACCORDINGLY. |
| | |
| | |
| | |
| | 2) SHEET LS 1.1 - THERE IS AN ASSEMBLY AREA INDICATED |
| | WITH TWO EXITS; ONE AT THE FRONT DOOR AND ONE THROUGH |
| | THE STORAGE AREA. THE ASSEMBY AREA EXIT CAN NOT PASS |
| | THROUGH A HIGHER HAZARD AREA, LIKE STORAGE. |
| | |
| | PER NFPA 101 CH 7, MEANS OF EGRESS |
| | |
| | 7.5.1.6 EXIT ACCESS FROM ROOMS OR SPACES SHALL BE |
| | PERMITTED TO BE |
| | THROUGH ADJOINING OR INTERVENING ROOMS OR AREAS, |
| | PROVIDED THAT SUCH |
| | ROOMS OR AREAS ARE ACCESSORY TO THE AREA SERVED. |
| | FOYERS, LOBBIES, AND |
| | RECEPTION ROOMS CONSTRUCTED AS REQUIRED FOR CORRIDORS |
| | SHALL NOT BE |
| | CONSTRUED AS INTERVENING ROOMS. EXIT ACCESS SHALL BE |
| | ARRANGED SO |
| | THAT IT IS NOT NECESSARY TO PASS THROUGH ANY AREA |
| | IDENTIFIED UNDER |
| | PROTECTION FROM HAZARDS IN CHAPTERS 11 THROUGH 43. |
| | |
| | PER NFPA 101, CH 13 NEW ASSEMBLY OCCUPANCIES |
| | |
| | 12.2.5.2 ACCESS THROUGH HAZARDOUS AREAS. MEANS OF |
| | EGRESS |
| | FROM A ROOM OR SPACE FOR ASSEMBLY PURPOSES SHALL NOT BE |
| | PERMITTED THROUGH KITCHENS, STOREROOMS, RESTROOMS, |
| | CLOSETS, |
| | PLATFORMS, STAGES, PROJECTION ROOMS, OR HAZARDOUS AREAS |
| | AS |
| | DESCRIBED IN 12.3.2. |
| | |
| | ADDITIONALLY, THE REAR EXIT CANNOT BE USED AS THE 2ND |
| | EXIT FROM THE ASSEMBLY SPACE DUE TO THE REMOTENSS CODE |
| | BELOW. |
| | |
| | 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR |
| | EXIT DISCHARGE IS |
| | REQUIRED FROM A BUILDING OR PORTION THEREOF, SUCH |
| | EXITS, EXIT ACCESSES, |
| | OR EXIT DISCHARGES SHALL BE REMOTELY LOCATED FROM EACH |
| | OTHER AND BE |
| | ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE |
| | HAS THE |
| | POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR OTHER |
| | EMERGENCY |
| | CONDITION. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC |
| | DETAILS AND FIRE CODE REFERENCES. |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 4)ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | |
| | PETER LEDUC |