Plan Review Notes
Plan Review Notes For Permit 19070494
Permit Number 19070494
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-07-15 12:43:10THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET LS 1.1 - THERE APPEARS TO BE A NEW 1-HOUR WALL
 IS INDICATED WITHIN THE CENTER AREA OF THE BUILDING;
 HOWEVER THERE IS AN OPEN AREA AT THE FRONT DESK AREA.
  
 THERE IS NO NET FIRE SEPARATION FOR THIS NEW 1 HOUR
 WALL AND I'M NOT SURE OF THE DESING ATTEMPT.
  
 IS THIS A MIXED, SEPARATED OR NONSEPARATED OCCUPANCY?
  
 PER NFPA 101, CH 6, OCCUPANCY CLSSIFICATION
  
 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE
 IN WHICH TWO
 OR MORE CLASSES OF OCCUPANCY EXIST.
 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE
 THE
 OCCUPANCIES ARE INTERMINGLED.
 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY
 WHERE THE
 OCCUPANCIES ARE SEPARATED BY FIRE RESISTANCE?RATED
 ASSEMBLIES.
 6.1.14.3 MIXED OCCUPANCIES.
 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE
 CLASSIFIED AS TO ITS USE IN
 ACCORDANCE WITH SECTION 6.1.
 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST
 RESTRICTIVE
 REQUIREMENTS OF THE OCCUPANCIES INVOLVED, UNLESS
 SEPARATE SAFEGUARDS
 ARE APPROVED.
 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.)
 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED,
 EACH PART OF THE
 BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED
 IN THIS CHAPTER,
 SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY
 FIRE-RESISTIVE
 ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3,
 TABLE 6.1.14.4.1(A),
 AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED
 BY APPROVED
 EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY
 6.1.14.4.6.
 6.1.14.4.2 OCCUPANCY SEPARATIONS SHALL BE CLASSIFIED AS
 3-HOUR FIRE
 RESISTANCE?RATED, 2-HOUR FIRE RESISTANCE?RATED, OR
 1-HOUR FIRE
 RESISTANCE?RATED AND SHALL MEET THE REQUIREMENTS OF
 CHAPTER 8.
 6.1.14.4.3 THE MINIMUM FIRE RESISTANCE RATING SPECIFIED
 IN TABLE
 6.1.14.4.1(A) AND TABLE 6.1.14.4.1(B) SHALL BE
 PERMITTED TO BE
 REDUCED BY 1 HOUR, BUT IN NO CASE SHALL IT BE REDUCED
 TO LESS THAN 1
 HOUR, WHERE THE BUILDING IS PROTECTED THROUGHOUT BY AN
 APPROVED
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 9.7.1.1(1) AND
 SUPERVISED IN ACCORDANCE WITH 9.7.2, UNLESS PROHIBITED
 BY THE
 DOUBLE-DAGGER FOOTNOTE ENTRIES IN THE TABLES.
 6.1.14.4.4 OCCUPANCY SEPARATIONS SHALL BE VERTICAL,
 HORIZONTAL, OR
 BOTH OR, WHEN NECESSARY, OF SUCH OTHER FORM AS REQUIRED
 TO PROVIDE
 COMPLETE SEPARATION BETWEEN OCCUPANCY DIVISIONS IN THE
 BUILDING.
 6.1.14.4.5* EACH SEPARATED PORTION OF THE BUILDING
 SHALL COMPLY
 WITH THE REQUIREMENTS FOR THE OCCUPANCY THEREIN.
  
 PLEASE CLARIFY AND CORRECT ACCORDINGLY.
  
  
  
 2) SHEET LS 1.1 - THERE IS AN ASSEMBLY AREA INDICATED
 WITH TWO EXITS; ONE AT THE FRONT DOOR AND ONE THROUGH
 THE STORAGE AREA. THE ASSEMBY AREA EXIT CAN NOT PASS
 THROUGH A HIGHER HAZARD AREA, LIKE STORAGE.
  
 PER NFPA 101 CH 7, MEANS OF EGRESS
  
 7.5.1.6 EXIT ACCESS FROM ROOMS OR SPACES SHALL BE
 PERMITTED TO BE
 THROUGH ADJOINING OR INTERVENING ROOMS OR AREAS,
 PROVIDED THAT SUCH
 ROOMS OR AREAS ARE ACCESSORY TO THE AREA SERVED.
 FOYERS, LOBBIES, AND
 RECEPTION ROOMS CONSTRUCTED AS REQUIRED FOR CORRIDORS
 SHALL NOT BE
 CONSTRUED AS INTERVENING ROOMS. EXIT ACCESS SHALL BE
 ARRANGED SO
 THAT IT IS NOT NECESSARY TO PASS THROUGH ANY AREA
 IDENTIFIED UNDER
 PROTECTION FROM HAZARDS IN CHAPTERS 11 THROUGH 43.
  
 PER NFPA 101, CH 13 NEW ASSEMBLY OCCUPANCIES
  
 12.2.5.2 ACCESS THROUGH HAZARDOUS AREAS. MEANS OF
 EGRESS
 FROM A ROOM OR SPACE FOR ASSEMBLY PURPOSES SHALL NOT BE
 PERMITTED THROUGH KITCHENS, STOREROOMS, RESTROOMS,
 CLOSETS,
 PLATFORMS, STAGES, PROJECTION ROOMS, OR HAZARDOUS AREAS
 AS
 DESCRIBED IN 12.3.2.
  
 ADDITIONALLY, THE REAR EXIT CANNOT BE USED AS THE 2ND
 EXIT FROM THE ASSEMBLY SPACE DUE TO THE REMOTENSS CODE
 BELOW.
  
 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR
 EXIT DISCHARGE IS
 REQUIRED FROM A BUILDING OR PORTION THEREOF, SUCH
 EXITS, EXIT ACCESSES,
 OR EXIT DISCHARGES SHALL BE REMOTELY LOCATED FROM EACH
 OTHER AND BE
 ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE
 HAS THE
 POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR OTHER
 EMERGENCY
 CONDITION.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC
 DETAILS AND FIRE CODE REFERENCES.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4)ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  