Plan Review Notes
Plan Review Notes For Permit 19070494
Permit Number 19070494
Review Stop B
Sequence Number 1
Notes
Date Text
2019-08-19 07:29:122017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19070494
 ADD: 1921 S DIXIE HWY.
 CONT: CONKLING & LEWIS CONSTRUCTION
 TEL: 561-833-4441
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. AUGUST 13, 2019
 ACTION: DENIED
  
 1) THE LS-1.1 FIRST FLOOR LIFE SAFETY SHEET:
 1A) THE CODE DATA HAS REQUIREMENTS FOR TABLE 601 FOR
 BUILDING ELEMENTS BUT NOT FOR:
  
 1A)(1) MISSING THE REQUIREMENTS FROM THE 2017 FBC-B
 TABLE 602 THE FIRE RESISTANCE REQUIREMENTS FOR EXTERIOR
 WALLS BASED ON FIRE SEPARATION DISTANCE.
  
 1A)(2) THE SURVEY INDICATES THIS IS A 2 STORY BUILDING
 PLEASE ALSO CONSIDER THE REQUIREMENTS FOR FIRE
 RESISTANCE RATING REQUIREMENTS FOR HORIZONTAL
 ASSEMBLIES BETWEEN FIRE AREAS, TABLE 707.3.10 OF THE
 2017 FBC-B. PLEASE PROVIDE WHAT OCCUPANCY IS ON THE 2ND
 FLOOR TO KNOW WHAT THE FIRE RESISTANCE RATING SHOULD
 BE? ON THE LIFE SAFETY SHEET THE CODE DATA STATES THE
 BUILDING IS A ONE STORY, IF SO THEN PLEASE UPDATE THE
 SURVEY. DISCREPANCY IN DOCUMENTS. 107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 1B) OCCUPANT LOADS BUSINESS & MERCANTILE IN BOTH CASES
 THE OCCUPANT LOAD WAS ROUNDED UP TO THE NEXT WHOLE
 NUMBER, THE OCCUPANT LOAD IS ROUNDED DOWN, AND THERE
 ARE NO PARTS OF OCCUPANTS. THE OCCUPANT LOAD IS ALWAYS
 ROUNDED DOWN TO THE NEXT WHOLE NUMBER TABLE 1004.1.2 OF
 THE 2017 FBC AND BUILDING OFFICIALS INFORMAL
 INTERPRETATION.
  
 1C) THE LIFE SAFETY SHEET UNDER THE HEADING OF OCCUPANT
 LOAD THE TOTAL OCCUPANT LOAD STATED IS 84 REQUIRING 2
 EXIT DOORS. THE BUILDING IS STATED AS BEING FIRE
 SPRINKLERED ALLOWING THE 2 EXITS TO BE AT LEAST 1/3 THE
 OVERALL DISTANCE APART. THE OVERALL DIAGONAL DISTANCE
 IS STATED ON THE PLANS AS 121 FEET. IN THE 2017 FBC-B
 SECTION 1007.1.1 EXCEPTION 2 ALLOWS WHEN 2 EXITS ARE
 REQUIRED FOR FULLY SPRINKLERED BUILDINGS THE SEPARATION
 DISTANCE CAN BE REDUCED TO 1/3RD OF THE LENGTH OF THE
 OVERALL DIAGONAL DISTANCE. THE MINIMUM OVERALL 1/3RD
 THE DIAGONAL DISTANCE APART FOR EXITS IS 40.333 FEET
 APART. PLEASE NOTE NEITHER OF THESE EXITS MEET THAT
 REQUIREMENT AS SHOWN THEY ARE 32.5 FEET AND 33.5 FEET
 APART AS SHOWN ON THE PLAN. THIS IS NOT TRUE. IN
 MEASURING THE DISTANCE BETWEEN THE EXITS, YOU DO NOT
 CUT THAT DISTANCE IN 1/3RD. PLEASE PROVIDE THE ACTUAL
 DISTANCE THE EXITS ARE SEPARATED, THIS IS THE DISTANCE
 THAT NEEDS TO BE SHOWN AND THAT DISTANCE WILL BE OVER
 40.333 FEET APART. CORRECT PLANS PLEASE SHOWING CODE
 COMPLIANCE.
  
 1D) THE LOWER LEFT SIDE OF THE SHEET THE COMMON PATH OF
 TRAVEL IS SHOWN AS 27.66 FEET. COMMON PATH OF TRAVEL
 FOR THIS AREA IS APPROXIMATELY 69 FEET. IT IS TAKEN IN
 THE MOST REMOTE POINT IN THE OFFICE AND MEASURED AT ONE
 FOOT OFF THE WALL OR TWO FEET OFF THE WALL TO THE POINT
 WHERE YOU HAVE A CHOICE OF 2 EGRESS PATHS. SEE IN THE
 2017 FBC-B SECTION 1006.2.1 AND TABLE 1006.2.1. PLEASE
 UPDATE THE TRAVEL DISTANCE FOR THE COMMON PATH OF
 TRAVEL.
  
 2) SHEET A1-1.5 1ST FLOOR CEILING PLAN SHOWS AN EXPOSED
 CEILING IN MANY PORTIONS OF THE BUILDING. WHEREAS THE
 SURVEY INDICATES THIS TO BE A 2 STORY BUILDING.
 RESTATED FROM COMMENT 1A)(2). HOW WILL THE REQUIREMENTS
 FOR FIRE RESISTANCE RATING REQUIREMENTS FOR HORIZONTAL
 ASSEMBLIES BETWEEN FIRE AREAS, TABLE 707.3.10 OF THE
 2017 FBC-B. PLEASE PROVIDE WHAT OCCUPANCY IS ON THE 2ND
 FLOOR TO KNOW WHAT THE FIRE RESISTANCE RATING SHOULD
 BE? ON THE LIFE SAFETY SHEET THE CODE DATA STATES THE
 BUILDING IS A ONE STORY, IF SO THEN PLEASE UPDATE THE
 SURVEY. DISCREPANCY IN DOCUMENTS. 107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3) SHEET A9.02 ACCESSIBLE RESTROOMS:
 3A) THE DETAIL # 7 SHOWS THE GRAB BAR BEING MEASURED
 FROM THE FLOOR TO THE CENTERLINE OF THE GRAB BAR.
 PLEASE NOTE THEE MEASUREMENT IS TO BE TAKEN FROM THE
 TOP OF THE GRASPING SURFACE. 2017 FBC-ACCESSIBILITY
 CODE SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS
 SHALL BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES
 MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 MEASURED TO THE TOP OF THE GRIPPING SURFACE, NOT
 CENTERLINE.
  
 3B) THE DETAIL # 7 SHOWS THE TOILET PAPER HOLDER
 VERTICAL DIMENSION BUT NOT THE HORIZONTAL DIMENSION
 FROM THE FRONT OF THE WATER CLOSET. TOILET PAPER
 DISPENSERS. 604.7 DISPENSERS. TOILET PAPER DISPENSERS
 SHALL COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM
 AND 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER. THE OUTLET
 OF THE DISPENSER SHALL BE 15 INCHES MINIMUM AND 48
 INCHES MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE
 LOCATED BEHIND GRAB BARS. DISPENSERS SHALL NOT BE OF A
 TYPE THAT CONTROLS DELIVERY OR THAT DOES NOT ALLOW
 CONTINUOUS PAPER FLOW.
  
  
 3C) MEN?S RESTROOM DETAIL # 6 SHOWS A HEIGHT OF 39
 INCHES TO WHAT APPEARS TO BE A SHELF BELOW THE EDGE LIT
 MIRROR, PLEASE BE AWARE THAT MIRRORS ARE TO BE LOCATED
 ABOVE LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH
 THE BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 4) THE STRUCTURAL SHEETS SHOW THE USE OF STEEL COLUMNS,
 BEAMS AND ROOF DECKING. PLEASE SHOW COMPLIANCE WITH
 WELDED AND BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION. IN ACCORDANCE WITH THE AMERICAN WELDING
 SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS
 FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
  
 5) SHEET A3.02, A7.03 BOTH SHOW NEW EXTERIOR DOORS, AND
 MULLIONS, PLEASE PROVIDE COMPLIANCE WITH:
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS.
 (B) WINDOWS & MULLIONS.
 (C) PANEL WALLS: STOREFRONTS SYSTEMS.
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS
 6) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 7) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 8) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  