| Plan Review Notes For Permit 19070471 |
| Permit Number |
19070471 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-08-16 14:13:18 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | 2ND BUILDING REVIEW DENIED: | | | | | | THE EGRESS EXITS ARE STILL IN QUESTION. | | | | | | PLEASE CLARIFY: | | | | | | THE FOLLOWING NEED TO BE CLARIFIED TO ENSURE CODE | | | COMPLIANT EGRESS: | | | | | | 1. ADD DIMENSIONS TO EACH OPENING. | | | 2. PROVIDE OCCUPANCY CLASSIFICATION AND OCCUPANYT LOAD | | | OR PROVIDE BUILDING USE. | | | 3. PROVIDE CLARITY ON INTERIOR, IT APPEARS THAT THERE | | | ARE POSSIBLY INTERIOR TENANT SEPERATION WALLS. |
|