2019-07-31 06:09:28ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO DISCONNECT SHOWN CONFORMING TO DISCONNECT
 REQUIREMENTS OF NEC 600.6A1, ONLY A NOTE. SHOW
 DISCONNECT ON PLAN, MUST BE WITHIN SIGHT OF SIGN.
  
 2. NOTE ON PLAN ABOUT TIMECLOCK OR PHOTOCELL REFERENCES
 SFBC NOT FBC EC AND DOES NOT CONFORM TO ENERGY
 CONSERVATION STANDARDS OF FBC EC 405.2.5, ALL TIME
 SWITCHES MUST RETAIN TIME SETTING FOR MINIMUM OF 10
 HOURS FOLLOWING A LOSS OF POWER. PLEASE CORRECT NOTE.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  