2019-10-07 18:53:27PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NOT ADDRESSED. THIS PROJECT IS LOCATED IN A SPECIAL
 FLOOD HAZARD AREA "AE" WITH A BASE FLOOD ELEVATION OF
 6' BFE NAVD 88 PLUS A 2' FREEBOARD. BASED ON THE VALUE
 OF THIS PROJECT COMBINED WITH IMPROVEMENTS MADE OVER
 THE LAST FIVE YEARS, THIS WILL BE A SUBSTANTIAL
 IMPROVEMENT TO A PRE-FIRM STRUCTURE. SUBMIT TWO SETS OF
 A PRE CONSTRUCTION ELEVATION CERTIFICATE BASED ON THE
 CONSTRUCTION DRAWINGS. SHOW HOW THE PROPOSED GARAGE
 WILL COMPLY WITH FBC-R322 AND THE CITY OF WEST PALM
 BEACH'S FLOOD ORDINANCE. SEE FEMA DOCUMENT P-758
 SUBSTANTIAL IMPROVEMENT/SUBSTANTIAL DAMAGE DESK
 REFERENCE FOR GUIDANCE.
  
 2) NOT ADDRESSED. FBC 107.3.4 - PROVIDE TWO SETS OF
 PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE
 REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE
 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE
 PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING
 INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES
 FOR EACH OF THE DIFFERENT ROOFING MATERIALS, WINDOWS
 (GLASS TYPES), STRUCTURAL MULLIONS AND EXTERIOR DOOR
 TYPES.
  
 3) COMPLIED.
  
 4) COMPLIED.
  
 5) NOT ADDRESSED. NEW PAGE 4.1 WITH NEW DATE WAS NOT
 SUBMITTED. THIS ON THE WALL SECTION ON SHEET 4.1, THE
 ROOF MATERIAL NOTES SPECIFY A METAL ROOF ON 30# FELT
 OVER 90# FELT HOT MOPPED. IS THIS CORRECT? PLEASE
 CLARIFY. FBC 107.2.1
  
 6) NOT ADDRESSED. NEW PAGE 4.1 WITH NEW DATE WAS NOT
 SUBMITTED. THE WINDOW INFILL DETAIL WILL NEED TO SHOW
 THE R-VALUE OF THE WALL INSULATION AS REQUIRED BY FBC
 ENERGY CONSERVATION R401.
  
 7) NOT ADDRESSED. THE ROOF ZONE PRESSURES IN THE
 SCHEDULE APPEAR TO BE FOR A FLAT ROOF RATHER THAN A
 5/12 SLOPED ROOF WHICH IS THE CASE WITH THIS PROJECT.
 FBC-R301.2.1
  
 8) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 9) NEW COMMENT. SPECIFY THE FINISHED FLOOR ELEVATIONS
 ON THE PLANS USING NAVD 88 DATUM. FBC 107.2.1
  
 10) NEW COMMENT. SHOW THE ELEVATIONS OF THE ENGINEERED
 FLOOD VENTS ON THE PLANS. FBC-R322.2.2.1
  
 11) NEW COMMENT. PROVIDE THE CALCULATIONS ON THE PLANS
 TO SHOW THAT THE REQUIRED CLEAR AREA OF FLOOD VENTS HAS
 BEEN PROVIDED. FBC-R322.2.2
  
 12) NEW COMMENT. SPECIFY ON THE PLANS THAT THIS PROJECT
 IS A NOT STRUCTURALLY CONNECTED LATERAL ADDITION TO A
 PRE-FIRM BUILDING. FBC 107.2.1
  
 13) NEW COMMENT. A NEW PAGE C.1 WITH THE NEW DATE WAS
 NOT SUBMITTED. FBC 107.2.1
  
  
  
  
  
  
  