| 2019-10-07 18:53:27 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) NOT ADDRESSED. THIS PROJECT IS LOCATED IN A SPECIAL |
| | FLOOD HAZARD AREA "AE" WITH A BASE FLOOD ELEVATION OF |
| | 6' BFE NAVD 88 PLUS A 2' FREEBOARD. BASED ON THE VALUE |
| | OF THIS PROJECT COMBINED WITH IMPROVEMENTS MADE OVER |
| | THE LAST FIVE YEARS, THIS WILL BE A SUBSTANTIAL |
| | IMPROVEMENT TO A PRE-FIRM STRUCTURE. SUBMIT TWO SETS OF |
| | A PRE CONSTRUCTION ELEVATION CERTIFICATE BASED ON THE |
| | CONSTRUCTION DRAWINGS. SHOW HOW THE PROPOSED GARAGE |
| | WILL COMPLY WITH FBC-R322 AND THE CITY OF WEST PALM |
| | BEACH'S FLOOD ORDINANCE. SEE FEMA DOCUMENT P-758 |
| | SUBSTANTIAL IMPROVEMENT/SUBSTANTIAL DAMAGE DESK |
| | REFERENCE FOR GUIDANCE. |
| | |
| | 2) NOT ADDRESSED. FBC 107.3.4 - PROVIDE TWO SETS OF |
| | PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE |
| | REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE |
| | 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE |
| | PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING |
| | INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES |
| | FOR EACH OF THE DIFFERENT ROOFING MATERIALS, WINDOWS |
| | (GLASS TYPES), STRUCTURAL MULLIONS AND EXTERIOR DOOR |
| | TYPES. |
| | |
| | 3) COMPLIED. |
| | |
| | 4) COMPLIED. |
| | |
| | 5) NOT ADDRESSED. NEW PAGE 4.1 WITH NEW DATE WAS NOT |
| | SUBMITTED. THIS ON THE WALL SECTION ON SHEET 4.1, THE |
| | ROOF MATERIAL NOTES SPECIFY A METAL ROOF ON 30# FELT |
| | OVER 90# FELT HOT MOPPED. IS THIS CORRECT? PLEASE |
| | CLARIFY. FBC 107.2.1 |
| | |
| | 6) NOT ADDRESSED. NEW PAGE 4.1 WITH NEW DATE WAS NOT |
| | SUBMITTED. THE WINDOW INFILL DETAIL WILL NEED TO SHOW |
| | THE R-VALUE OF THE WALL INSULATION AS REQUIRED BY FBC |
| | ENERGY CONSERVATION R401. |
| | |
| | 7) NOT ADDRESSED. THE ROOF ZONE PRESSURES IN THE |
| | SCHEDULE APPEAR TO BE FOR A FLAT ROOF RATHER THAN A |
| | 5/12 SLOPED ROOF WHICH IS THE CASE WITH THIS PROJECT. |
| | FBC-R301.2.1 |
| | |
| | 8) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | 9) NEW COMMENT. SPECIFY THE FINISHED FLOOR ELEVATIONS |
| | ON THE PLANS USING NAVD 88 DATUM. FBC 107.2.1 |
| | |
| | 10) NEW COMMENT. SHOW THE ELEVATIONS OF THE ENGINEERED |
| | FLOOD VENTS ON THE PLANS. FBC-R322.2.2.1 |
| | |
| | 11) NEW COMMENT. PROVIDE THE CALCULATIONS ON THE PLANS |
| | TO SHOW THAT THE REQUIRED CLEAR AREA OF FLOOD VENTS HAS |
| | BEEN PROVIDED. FBC-R322.2.2 |
| | |
| | 12) NEW COMMENT. SPECIFY ON THE PLANS THAT THIS PROJECT |
| | IS A NOT STRUCTURALLY CONNECTED LATERAL ADDITION TO A |
| | PRE-FIRM BUILDING. FBC 107.2.1 |
| | |
| | 13) NEW COMMENT. A NEW PAGE C.1 WITH THE NEW DATE WAS |
| | NOT SUBMITTED. FBC 107.2.1 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |