| 2019-07-15 14:35:03 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET A 100 - THE OCCUPANCY IS INDICATED AS |
| | MERCANTILE AND STORAGE; HOWEVER, IT IS NOT INDICATED AS |
| | MIXED, SEPARATED OR NON-SEPARATED. |
| | |
| | PER NFPA 101, CH 6 OCCUPANCY CLASSIFICATION |
| | |
| | 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE |
| | IN WHICH TWO |
| | OR MORE CLASSES OF OCCUPANCY EXIST. |
| | 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE |
| | THE |
| | OCCUPANCIES ARE INTERMINGLED. |
| | 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY |
| | WHERE THE |
| | OCCUPANCIES ARE SEPARATED BY FIRE RESISTANCE?RATED |
| | ASSEMBLIES. |
| | 6.1.14.3 MIXED OCCUPANCIES. |
| | 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE |
| | CLASSIFIED AS TO ITS USE IN |
| | ACCORDANCE WITH SECTION 6.1. |
| | 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST |
| | RESTRICTIVE |
| | REQUIREMENTS OF THE OCCUPANCIES INVOLVED, UNLESS |
| | SEPARATE SAFEGUARDS |
| | ARE APPROVED. |
| | 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.) |
| | 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED, |
| | EACH PART OF THE |
| | BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED |
| | IN THIS CHAPTER, |
| | SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY |
| | FIRE-RESISTIVE |
| | ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3, |
| | TABLE 6.1.14.4.1(A), |
| | AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED |
| | BY APPROVED |
| | EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY |
| | 6.1.14.4.6. |
| | 6.1.14.4.2 OCCUPANCY SEPARATIONS SHALL BE CLASSIFIED AS |
| | 3-HOUR FIRE |
| | RESISTANCE?RATED, 2-HOUR FIRE RESISTANCE?RATED, OR |
| | 1-HOUR FIRE |
| | RESISTANCE?RATED AND SHALL MEET THE REQUIREMENTS OF |
| | CHAPTER 8. |
| | 6.1.14.4.3 THE MINIMUM FIRE RESISTANCE RATING SPECIFIED |
| | IN TABLE |
| | 6.1.14.4.1(A) AND TABLE 6.1.14.4.1(B) SHALL BE |
| | PERMITTED TO BE |
| | REDUCED BY 1 HOUR, BUT IN NO CASE SHALL IT BE REDUCED |
| | TO LESS THAN 1 |
| | HOUR, WHERE THE BUILDING IS PROTECTED THROUGHOUT BY AN |
| | APPROVED |
| | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH |
| | 9.7.1.1(1) AND |
| | SUPERVISED IN ACCORDANCE WITH 9.7.2, UNLESS PROHIBITED |
| | BY THE |
| | DOUBLE-DAGGER FOOTNOTE ENTRIES IN THE TABLES. |
| | 6.1.14.4.4 OCCUPANCY SEPARATIONS SHALL BE VERTICAL, |
| | HORIZONTAL, OR |
| | BOTH OR, WHEN NECESSARY, OF SUCH OTHER FORM AS REQUIRED |
| | TO PROVIDE |
| | COMPLETE SEPARATION BETWEEN OCCUPANCY DIVISIONS IN THE |
| | BUILDING. |
| | 6.1.14.4.5* EACH SEPARATED PORTION OF THE BUILDING |
| | SHALL COMPLY |
| | WITH THE REQUIREMENTS FOR THE OCCUPANCY THEREIN. |
| | |
| | PLEASE PROVIDE THE OCCUPANCY CLASSIFICATION PER THE |
| | ABOVE. |
| | |
| | |
| | |
| | 2) SHEET A 100 - THERE APPEARS TO BE A SEPARATION WALL |
| | BETWEEN THE MERCANTILE AND WAREHOUSE/STORAGE. |
| | |
| | THERE IS NO FIRE RATING OF THE EXISTING WALL. |
| | |
| | PLEASE PROVIDE THIS FIRE RATING PER # 1 ABOVE OR |
| | JUSTIFY WITH SPECIFIC DETAIL AND CODE REFERENCES. |
| | |
| | |
| | |
| | 3) SHEET A 101 - DOOR 130 IS INDICATED WITHIN THE |
| | SEPARATION WALL; BUT THE DOOR SCHEDULE ON SHEET A 103 |
| | INDICATES A 1 HOUR FIRE RATED DOOR. |
| | |
| | THE REQUIRED SEPARATION PER # 1 ABOVE IS 2 HOUR. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC |
| | DETAIL AND CODE REFERENCES. |
| | |
| | |
| | |
| | |
| | 4) SHEET A 101 - THE SMALL STORAGE ROOM HAS A WALL |
| | IN-FILL SEPARATING IT FORM THE WAREHOUSE WITH A C |
| | CALL-OUT. SHEET A 103 INDICATED THE C CALL-OUT AS 1 |
| | HOUR. |
| | |
| | THE REQUIRED SEPARATION PER # 1 ABOVE IS 2 HOUR. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC |
| | DETAIL AND CODE REFERENCES. |
| | |
| | |
| | |
| | 5) SHEET A 103 - THE IS NO DOOR EXIT HARDWARE INDICATED |
| | ON THE DOOR SCHEDULE. |
| | |
| | PLEASE PROVIDE EXIT DOOR HARDWARE PER NFPA 101, CH 7, |
| | MEANS OF EGRESS. |
| | |
| | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM |
| | THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY |
| | TO DOOR |
| | LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO |
| | ELEVATED |
| | TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON |
| | LABORATORY |
| | FIRE TEST PROCEDURES. |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A |
| | TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM |
| | THE EGRESS |
| | SIDE. |
| | 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3 |
| | SHALL NOT |
| | APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH |
| | 23. |
| | |
| | 7.2.1.5.10* A LATCH OR OTHER FASTENING DEVICE ON A DOOR |
| | LEAF SHALL |
| | BE PROVIDED WITH A RELEASING DEVICE THAT HAS AN OBVIOUS |
| | METHOD OF |
| | OPERATION AND THAT IS READILY OPERATED UNDER ALL |
| | LIGHTING CONDITIONS. |
| | 7.2.1.5.10.1 THE RELEASING MECHANISM FOR ANY LATCH |
| | SHALL BE |
| | LOCATED AS FOLLOWS: |
| | (1) NOT LESS THAN 34 IN. (865 MM) ABOVE THE FINISHED |
| | FLOOR FOR |
| | OTHER THAN EXISTING INSTALLATIONS |
| | (2) NOT MORE THAN 48 IN. (1220 MM) ABOVE THE FINISHED |
| | FLOOR |
| | 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN THE |
| | DOOR LEAF |
| | WITH NOT MORE THAN ONE RELEASING OPERATION, UNLESS |
| | OTHERWISE |
| | SPECIFIED IN 7.2.1.5.10.3, 7.2.1.5.10.4, OR |
| | 7.2.1.5.10.6. |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS. |
| | |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |