| 2020-01-13 11:23:18 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19070407 |
| | 2 ND REVIEW: JANUARY 13, 2020 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK |
| | BELOW) |
| | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ |
| | BUILDING-PERMIT-FORMS |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | FBC[R] = FBC RESIDENTIAL |
| | |
| | *FROM PREVIOUS REVIEW. ELEVATION CERTIFICATE WAS NOT |
| | PROVIDED. THE COMMENT IS NOW UNDER THE NFIP STOP. |
| | |
| | 1) 109.3 FBC[AMENDED]PROVIDE UPDATED VALUE OF PROPOSED |
| | WORK WITH SCOPE CHANGE INCLUDED. THE PREVIOUS VALUE WAS |
| | $300,000.00 BEFORE ADDING RAISED FLOOR, WALLS AND |
| | CEILING. |
| | |
| | 2) 408.4 FBC[R] ACCESS TO UNDER FLOOR SPACE. ACCESS |
| | OPENINGS THROUGH THE FLOOR SHALL BE A MINIMUM OF 18 |
| | INCHES BY 24 INCHES. OPENINGS THROUGH A PERIMETER WALL |
| | SHALL BE NOT LESS THAN 16 INCHES BY 24 INCHES. |
| | -PLEASE SHOW WHERE THIS ACCESS WILL BE PROVIDED. |
| | |
| | 3) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR |
| | WINDOWS, WINDOW MULL, DOORS, TRANSOMS, SLIDERS AND |
| | SOLAR TUBES, OR INDICATE THAT YOU WOULD LIKE THEM |
| | DEFERRED. |
| | |
| | 4) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR |
| | ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM DEFERRED. |
| | |
| | 5) 107.2.1.2 FBC[AMENDED] PROVIDE STAIRCASE AND GUARD |
| | RAIL ENGINEERING, OR INDICATE THAT IT WILL BE DEFERRED. |
| | |
| | 6) 107.3.4.1 FBC[AMENDED] SUBMIT TRUSS SHOP DRAWINGS TO |
| | THE BUILDING INSPECTOR PRIOR TO INSTALLATION. |
| | -NO RESPONSE NEEDED FOR THIS COMMENT. |
| | |
| | WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |