Plan Review Notes
Plan Review Notes For Permit 19070407
Permit Number 19070407
Review Stop M
Sequence Number 1
Notes
Date Text
2019-10-29 12:23:421ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19070407
 10/29/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW AC SYSTEMS #1 & #2- SECTION R403.6.1 FBC EC.
  
 2) THE CONVERSION OF THE GARAGE TO NEW CONDITIONED
 LIVING SPACE IS CLASSIFIED AS AN ADDITION PER SECTION
 R202 FBC EC. PLEASE SUBMIT AN ENERGY COMPLIANCE REPORT-
 SECTION C101.5.1 FBC EC.
  
 3) SHEET M-200:THE KITCHEN HOOD EXHAUST NOTE REFERENCES
 SECTION M1503.4 WHICH IS THE MAKEUP AIR REQUIREMENT FOR
 HOODS EXCEEDING 400 CFMS OF EXHAUST. PLEASE CORRECT THE
 CODE REFERENCE, OR INDICATE HOW MAKEUP WILL BE
 PROVIDED. PLEASE NOTE THAT TYPE 1 HOODS ARE NOT
 REQUIRED FOR DOMESTIC COOKING APPLIANCES. A TYPE 1 IS A
 COMMERCIAL GREASE EXHAUST HOOD- SECTION 507.2 FBC M.
  
 4) PLEASE REFER TO THE BUILDING REVIEW COMMENTS- THE
 NEW CU'S SHALL BE INSTALLED AT OR ABOVE BASE FLOOD
 ELEVATION PER SECTION R322.1.6 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  