| 2019-10-29 12:23:42 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19070407 |
| | 10/29/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SUBMIT AC COOLING AND HEATING CALCULATIONS FOR THE |
| | NEW AC SYSTEMS #1 & #2- SECTION R403.6.1 FBC EC. |
| | |
| | 2) THE CONVERSION OF THE GARAGE TO NEW CONDITIONED |
| | LIVING SPACE IS CLASSIFIED AS AN ADDITION PER SECTION |
| | R202 FBC EC. PLEASE SUBMIT AN ENERGY COMPLIANCE REPORT- |
| | SECTION C101.5.1 FBC EC. |
| | |
| | 3) SHEET M-200:THE KITCHEN HOOD EXHAUST NOTE REFERENCES |
| | SECTION M1503.4 WHICH IS THE MAKEUP AIR REQUIREMENT FOR |
| | HOODS EXCEEDING 400 CFMS OF EXHAUST. PLEASE CORRECT THE |
| | CODE REFERENCE, OR INDICATE HOW MAKEUP WILL BE |
| | PROVIDED. PLEASE NOTE THAT TYPE 1 HOODS ARE NOT |
| | REQUIRED FOR DOMESTIC COOKING APPLIANCES. A TYPE 1 IS A |
| | COMMERCIAL GREASE EXHAUST HOOD- SECTION 507.2 FBC M. |
| | |
| | 4) PLEASE REFER TO THE BUILDING REVIEW COMMENTS- THE |
| | NEW CU'S SHALL BE INSTALLED AT OR ABOVE BASE FLOOD |
| | ELEVATION PER SECTION R322.1.6 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |