| Plan Review Notes For Permit 19070407 |
| Permit Number |
19070407 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-07-18 17:37:19 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. AN INTERIOR DEMO PERMIT CANNOT BE ISSUED UNTIL AFTER | | | THE REMODEL PLANS ARE SUBMITTED AND REVIEWED IN ORDER | | | TO VERIFY THAT THE PROPOSED IMPROVEMENT WILL NOT | | | CONSTITUTE A SUBSTANTIAL IMPROVEMENT, FBC EB 701.3. | | | BASED ON THE DEMO PLAN SUBMITTED, RENOVATION WILL BE | | | EXTENSIVE AND WILL LIKELY EXCEED 50% THE VALUE OF THE | | | STRUCTURE. | | | | | | ALTERNATIVELY, YOU CAN SEND A CURRENT ELEVATION | | | CERTIFICATE TO SHOW THAT THE STRUCTURE AND MECHANICAL | | | EQUIPMENT WILL MEET BFE + 2' FREEBOARD. | | | | | | YOU MAY FIND THE FOLLOWING DOCUMENT HELPFUL: | | | | | | HTTPS://WWW.FEMA.GOV/MEDIA-LIBRARY-DATA/20130726-1734-2 | | | 5045-2915/P_758_COMPLETE_R3.PDF | | | | | | SEE SECTION 4, ESPECIALLY 4.4 AND 4.5. ADDITIONAL | | | INFORMATION MAY BE SENT TO ME VIA EMAIL. | | | | | | 2. THE PLANS SHOW REMOVAL OF EXTERIOR COMPONENTS. THIS | | | IS NOT PERMITTED UNDER AN INTERIOR DEMO PERMIT. A | | | PERMIT TO REMOVE ROOF AND TRUSSES, WINDOWS, DOORS WILL | | | NOT BE ISSUED WITHOUT APPROVED PLANS AS TO HOW THEY | | | WILL BE RESTORED. |
|