Plan Review Notes
Plan Review Notes For Permit 19070386
Permit Number 19070386
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2019-08-22 12:38:108/22/19
  
  
 THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ALL GATE OPENINGS SHALL BE 20'.
  
 PER NFPA 1
  
 18.2.3.4.1 DIMENSIONS.
 18.2.3.4.1.1 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN
 UNOBSTRUCTED
 WIDTH OF NOT LESS THAN 20 FT (6.1 M).
  
 18.2.4.1.2 MINIMUM REQUIRED WIDTHS AND CLEARANCES
 ESTABLISHED UNDER
 18.2.3.4 SHALL BE MAINTAINED AT ALL TIMES.
 18.2.4.1.3* FACILITIES AND STRUCTURES SHALL BE
 MAINTAINED IN A MANNER
 THAT DOES NOT IMPAIR OR IMPEDE ACCESSIBILITY FOR FIRE
 DEPARTMENT
 OPERATIONS.
 18.2.4.1.4 ENTRANCES TO FIRE DEPARTMENT ACCESS ROADS
 THAT HAVE BEEN
 CLOSED WITH GATES AND BARRIERS IN ACCORDANCE WITH
 18.2.4.2.1 SHALL NOT
 BE OBSTRUCTED BY PARKED VEHICLES
  
 PLEASE ENSURE REQUIRED WIDTH.
  
  
  
 2) FIRE KNOX PADLOCKS SHALL BE INSTALLED AT ALL GATES
 FOR 24 HR EMERGENCY ACCESS.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  