| Plan Review Notes For Permit 19070350 |
| Permit Number |
19070350 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-07-17 14:37:16 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) SHEET S 1 - THERE IS AN INDICATION OF 14' HEIGHT FOR | | | FIRE APPARATUS PARKING; HOWEVER THERE ANGLE BRACES | | | INDICATED ON BOTH SIDES THAT APPEAR TO ENCROACH ON THE | | | 14' AND NOT PROVIDE THE 13'6" MINIMUM HEIGHT | | | REQUIREMENT. | | | | | | PLEASE REVIEW AND CORRECT OR JUSTIFY THAT IT MEETS | | | MINIMUM MHEIGHT REQUIRMENTS. | | | | | | | | | 2) THERE DOES NO APPEAR TO BE ANY LIGHTING. THE | | | FPROPOSED DOES NOT MEET THE MINIMUM CANDELA LIGHTING | | | REQUIRED. | | | | | | WILL LIGHTING BE PROVIDED? | | | | | | PLEASE PROVIDE DETAILS. | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|