| 2020-03-13 19:15:01 | 03/13/2020 DISCUSSED WITH ROBERT BROWN (BUILDING |
| | OFFICIAL). |
| | |
| | THIRD BUILDING REVIEW CHECKLIST. |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- ENGINEERING FOR THE PRE-FAB GENERATOR PAD: |
| | |
| | A) DRAWING SUBMITTED DOESN'T HAVE THE ENGINEER'S |
| | ADDITIONAL INFORMATION REQUIRED BY 61G15-23.001(4) FAC. |
| | THE ENGINEER IS USING AN EMBOSSED SEAL, BUT THERE IS |
| | NOT A TITLE BLOCK SHOWING THE ENGINEER'S PRINTED |
| | INFORMATION AS REQUIRED BY 61G15-23.001(4) FAC. |
| | ALSO, CLARIFY WHY THE PREVIOUS ENGINEERING HAD A |
| | COMPLETE ENGINEER'S SIGNATURE BUT ENGINEERING SUBMITTED |
| | NOW HAVE ONLY THE ENGINEER'S INITIALS. |
| | (NOTE: THE ENGINEER'S NAME AND LICENSE NUMBER WILL NOT |
| | BE LEGIBLE WHEN SCANNING THIS DOCUMENT FOR RECORDS |
| | RETENTION BECAUSE THIS INFORMATION IS NOT PRINTED WHEN |
| | USING JUST AN EMBOSSED SEAL. SEC. 107.2.1.3 CITY |
| | AMENDMENTS). |
| | |
| | B) PLEASE CLARIFY WHY THE EQUIPMENT WEIGHT WAS |
| | INCREASED AND THE WIND LOADS WERE REDUCED BASED ON THE |
| | PREVIOUS SUBMITTAL IF THE EQUIPMENT WAS NOT CHANGED. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | C) PROVIDE TWO COPIES OF THE ENGINEERING. ONLY ONE COPY |
| | WAS PROVIDED. SEC. 107.1 CITY AMENDMENTS. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |