Plan Review Notes
Plan Review Notes For Permit 19070343
Permit Number 19070343
Review Stop B
Sequence Number 3
Notes
Date Text
2020-03-13 19:15:0103/13/2020 DISCUSSED WITH ROBERT BROWN (BUILDING
 OFFICIAL).
  
 THIRD BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- ENGINEERING FOR THE PRE-FAB GENERATOR PAD:
  
 A) DRAWING SUBMITTED DOESN'T HAVE THE ENGINEER'S
 ADDITIONAL INFORMATION REQUIRED BY 61G15-23.001(4) FAC.
 THE ENGINEER IS USING AN EMBOSSED SEAL, BUT THERE IS
 NOT A TITLE BLOCK SHOWING THE ENGINEER'S PRINTED
 INFORMATION AS REQUIRED BY 61G15-23.001(4) FAC.
 ALSO, CLARIFY WHY THE PREVIOUS ENGINEERING HAD A
 COMPLETE ENGINEER'S SIGNATURE BUT ENGINEERING SUBMITTED
 NOW HAVE ONLY THE ENGINEER'S INITIALS.
 (NOTE: THE ENGINEER'S NAME AND LICENSE NUMBER WILL NOT
 BE LEGIBLE WHEN SCANNING THIS DOCUMENT FOR RECORDS
 RETENTION BECAUSE THIS INFORMATION IS NOT PRINTED WHEN
 USING JUST AN EMBOSSED SEAL. SEC. 107.2.1.3 CITY
 AMENDMENTS).
  
 B) PLEASE CLARIFY WHY THE EQUIPMENT WEIGHT WAS
 INCREASED AND THE WIND LOADS WERE REDUCED BASED ON THE
 PREVIOUS SUBMITTAL IF THE EQUIPMENT WAS NOT CHANGED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 C) PROVIDE TWO COPIES OF THE ENGINEERING. ONLY ONE COPY
 WAS PROVIDED. SEC. 107.1 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]