Plan Review Notes
Plan Review Notes For Permit 19070343
Permit Number 19070343
Review Stop G
Sequence Number 1
Notes
Date Text
2019-07-22 07:22:077/22/2019 1ST GAS REVIEW**DENIED** WITH COMMENTS NOTE -
 A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC FUEL GAS SEC. 402.2
  
 2) SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE
 DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM 2017 FBC FUEL GAS SEC. 402.3
  
 3) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FBC FUEL GAS SEC.410.1
  
 4) THE CLAIMED VALUE INDICATED ON THE PERMIT
 APPLICATION DOES NOT MATCH THE PROVIDED BONA FIDE
 SIGNED CONTRACT. WPB AMENDMENTS TO THE FBC 109.3.
 BUILDING PERMITS VALUATIONS.
  
 5) THE GENERATOR SHALL BE ONE FOOT SIX INCHES (1?-6?)
 FROM THE HOUSE, FIVE (5?-0?) FROM THE PROPERTY LINE,
 EXHAUST SHALL BE TEN (10?-0?) FROM ANY OPENING UNLESS
 OTHERWISE STATED IN THE MANUFACTURES SPECIFICATION
 INSTRUCTIONS.
  
 6) SUBMIT TWO COPIES OF THE SURVEY INDICATING THE
 PROPOSED LOCATION OF THE NEW TANKLESS HEATER AND THE
 NEW GENERATOR. WPB AMENDMENTS TO THE FBC SEC. 107.2.1
  
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLANS EXAMINER
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  