Plan Review Notes
Plan Review Notes For Permit 19070343
Permit Number 19070343
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-07-24 13:28:48THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SITE PLAN - A REVIEW OF THE ACTUAL SITE AREA SHOWS
 FEATURES THAT ARE NOT INDICATED OF THE SUBMITTED
 DRAWINGS.
  
 THERE IS AN EXTERIOR CONCRETE WALL, ELECTRICAL
 DISCONNECTS AND WINDOWS ON THE PROPOSED EXTERIOR WALL
 LOCATION.
  
 PLEASE PROVIDE GREATER DETAIL WITH ALL APPLICABLE
 DIMENSIONS TO MORE ACTUALLY REFLECT EXISTING
 CONSTRUCTED FEATURES.
  
  
  
 2) THERE ARE NO FIRE CODE REFERENCES OF COMPLIANCE.
  
 THE INSTALL SHALL COMPLY WITH NFPA 110 AND NFPA 54.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE AN
 APPLICABLE CODE REFERENCE NOTE.
  
  
  
 3) WHAT CLASS OF TYPE IS THE PROPOSED GENERATOR AS THIS
 IS HOW IT WILL BE TESTED.
  
 PER NFPA 110
  
 CHAPTER 4 CLASSIFICATION OF EMERGENCY POWER SUPPLY
 SYSTEMS (EPSSS)
 4.1* GENERAL. THE EPSS SHALL PROVIDE A SOURCE OF
 ELECTRICAL
 POWER OF REQUIRED CAPACITY, RELIABILITY, AND QUALITY TO
 LOADS FOR
 A LENGTH OF TIME AS SPECIFIED IN TABLE 4.1(A) AND
 WITHIN A SPECIFIED
 TIME FOLLOWING LOSS OR FAILURE OF THE NORMAL POWER
 SUPPLY
 AS SPECIFIED IN TABLE 4.1(B).
 4.2* CLASS. THE CLASS DEFINES THE MINIMUM TIME, IN
 HOURS, FOR
 WHICH THE EPSS IS DESIGNED TO OPERATE AT ITS RATED LOAD
 WITHOUT
 BEING REFUELED OR RECHARGED. [SEE TABLE 4.1(A).]
 4.3 TYPE. THE TYPE DEFINES THE MAXIMUM TIME, IN
 SECONDS,
 THAT THE EPSS WILL PERMIT THE LOAD TERMINALS OF THE
 TRANSFER
 SWITCH TO BE WITHOUT ACCEPTABLE ELECTRICAL POWER. TABLE
 4.1(B)
 PROVIDES THE TYPES DEFINED BY THIS STANDARD.
 4.4* LEVEL. THIS STANDARD RECOGNIZES TWO LEVELS OF
 EQUIPMENT
 INSTALLATION, PERFORMANCE, AND MAINTENANCE.
 4.4.1* LEVEL 1 SYSTEMS SHALL BE INSTALLED WHERE FAILURE
 OF THE
 EQUIPMENT TO PERFORM COULD RESULT IN LOSS OF HUMAN LIFE
 OR
 SERIOUS INJURIES.
 4.4.2* LEVEL 2 SYSTEMS SHALL BE INSTALLED WHERE FAILURE
 OF THE
 EPSS TO PERFORM IS LESS CRITICAL TO HUMAN LIFE AND
 SAFETY.
 4.4.3 ALL EQUIPMENT SHALL BE PERMANENTLY INSTALLED.
 4.4.4* LEVEL 1 AND LEVEL 2 SYSTEMS SHALL ENSURE THAT
 ALL LOADS
 SERVED BY THE EPSS ARE SUPPLIED WITH ALTERNATE POWER
 THAT
 MEETS ALL THE FOLLOWING CRITERIA:
 (1) OF A QUALITY WITHIN THE OPERATING LIMITS OF THE
 LOAD
 (2) FOR A DURATION SPECIFIED FOR THE CLASS AS DEFINED
 IN TABLE
 4.1(A)
 (3) WITHIN THE TIME SPECIFIED FOR THE TYPE AS DEFINED
 IN TABLE
 4.1(B)
  
 PLEAE REVIEW AND PROVIDE DETAILS.
  
  
  
 4) PLEASE SHOW THE ROUTE OF THE NG LINE ON THE SITE
 PLAN, A SCHEMATIC IS PROVIDED BUT NOT THE ACTUAL ROUTE.
  
 ADDITIONALLY, PER NFPA 54
  
 7.1.2.1 COVER REQUIREMENTS. UNDERGROUND PIPING SYSTEMS
 SHALL BE INSTALLED WITH A MINIMUM OF 12 IN. (300 MM) OF
 COVER.
 (A) THE MINIMUM COVER SHALL BE INCREASED TO 18 IN.
 (460MM)IF
 EXTERNAL DAMAGE TO THE PIPE OR TUBING FROM EXTERNAL
 FORCES IS
 LIKELY TO RESULT.
 (B) WHERE A MINIMUM OF 12 IN. (300 MM) OF COVER CANNOT
 BE
 PROVIDED, THE PIPE SHALL BE INSTALLED IN CONDUIT OR
 BRIDGED
 (SHIELDED).
 7.1.3.2 UNDERGROUND PIPING SHALL COMPLY WITH ONE OR
 MORE
 OF THE FOLLOWING UNLESS APPROVED TECHNICAL
 JUSTIFICATION IS PROVIDED
 TO DEMONSTRATE THAT PROTECTION IS UNNECESSARY:
 (1) THE PIPING SHALL BE MADE OF CORROSION-RESISTANT
 MATERIAL THAT
 IS SUITABLE FOR THE ENVIRONMENT IN WHICH IT WILL BE
 INSTALLED.
 (2) PIPE SHALL HAVE A FACTORY-APPLIED, ELECTRICALLY
 INSULATING
 COATING. FITTINGS AND JOINTS BETWEEN SECTIONS OF COATED
 PIPE SHALL BE COATED IN ACCORDANCE WITH THE COATING
 MANUFACTURER?S
 INSTRUCTIONS.
 (3) THE PIPING SHALL HAVE A CATHODIC PROTECTION SYSTEM
 INSTALLED,
 AND THE SYSTEM SHALL BE MAINTAINED IN ACCORDANCE
 WITH 7.1.3.3 OR 7.1.3.6.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL