Plan Review Notes
Plan Review Notes For Permit 19070310
Permit Number 19070310
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-07-10 11:22:59THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) SHEET ID 0 - THERE IS NO REFERENCE TO COMPLIANCE
 WITH THE FLORIDA FIRE PREVENTION CODE.
  
 THE PROJECT SHALL COMPLY WITH THE 6TH EDITION OF THE
 FFPC
  
 PLEASE REVIEW AND ENSURE COMPLIANCE.
  
  
  
 2) SHEET ID 0 - UNER THE ELECTRICAL NOTES THERE IS AN
 INCORRECT EDITION REFERENCE.
  
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE.
  
  
  
  
 3) THERE ARE INDICATIONS OF FIRE SPRINKLER
 MODIFICATIONS.
  
 ANY WORK ON THE FIRE SPRINKLER OR FIRE ALARM SYSTEMS
 SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS.
  
 PLEASE ENSURE COMPLIANCE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL