| Plan Review Notes For Permit 19070310 |
| Permit Number |
19070310 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-07-10 11:22:59 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | | | | 1) SHEET ID 0 - THERE IS NO REFERENCE TO COMPLIANCE | | | WITH THE FLORIDA FIRE PREVENTION CODE. | | | | | | THE PROJECT SHALL COMPLY WITH THE 6TH EDITION OF THE | | | FFPC | | | | | | PLEASE REVIEW AND ENSURE COMPLIANCE. | | | | | | | | | | | | 2) SHEET ID 0 - UNER THE ELECTRICAL NOTES THERE IS AN | | | INCORRECT EDITION REFERENCE. | | | | | | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION. | | | | | | PLEASE REVIEW AND ENSURE COMPLIANCE. | | | | | | | | | | | | | | | 3) THERE ARE INDICATIONS OF FIRE SPRINKLER | | | MODIFICATIONS. | | | | | | ANY WORK ON THE FIRE SPRINKLER OR FIRE ALARM SYSTEMS | | | SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS. | | | | | | PLEASE ENSURE COMPLIANCE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|