| 2019-07-19 11:01:21 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH |
| | CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT "KITCHENS, |
| | LAUNDRY ROOMS", FAMILY ROOMS, DINING ROOMS, LIVING |
| | ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, |
| | RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS |
| | OR ROOMS, SHALL HAVE AFCI PROTECTION. |
| | NEC 210.12; FBC RE3902.16 |
| | |
| | E3902.7 SINK RECEPTACLES. 125-VOLT, SINGLE-PHASE, 15- |
| | AND 20-AMPERE RECEPTACLES THAT ARE LOCATED WITHIN 6 |
| | FEET (1829 MM) OF THE OUTSIDE EDGE OF A SINK SHALL HAVE |
| | GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR |
| | PERSONNEL |
| | |
| | E3902.8 BATHTUB OR SHOWER STALL RECEPTACLES. 125-VOLT, |
| | SINGLE PHASE, 15- AND 20-AMPERE RECEPTACLES THAT ARE |
| | LOCATED WITHIN 6 FEET (1829 MM) OF THE OUTSIDE EDGE OF |
| | A BATHTUB OR SHOWER STALL SHALL HAVE GROUND-FAULT |
| | CIRCUIT INTERRUPTER PROTECTION FOR PERSONNEL. |
| | [210.8(A)(8)] |
| | |
| | E3902.10 KITCHEN DISHWASHER BRANCH CIRCUIT. |
| | GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION SHALL BE |
| | PROVIDED FOR OUTLETS THAT SUPPLY DISHWASHERS IN |
| | DWELLING UNIT LOCATIONS. [210.8(D)] |
| | |
| | E3902.16 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION. |
| | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- |
| | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| | DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| | SHALL BE PROTECTED BY ANY OF THE FOLLOWING: [210.12(A)] |
| | |
| | 607.1.1RECEPTACLES. REPLACEMENT OF ELECTRICAL |
| | RECEPTACLES SHALL COMPLY WITH THE APPLICABLE |
| | REQUIREMENTS OF SECTION 406.4(D) OF NFPA 70 |
| | |