2019-07-25 06:09:53ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SOLAR PANELS NOT LISTED BY A NATIONALLY RECOGNIZED
 TESTING LABORATORY (NRTL) SUCH AS UL, CSA, INTEREK,
 ETC. VDE IS NOT A NRTL NEC 90.7, 110.2, 110.3B FBC
 107.2.1
  
 2. TWO SEPARATE PLANS PROVIDED. ONE IS SIGNED AND
 SEALED BY AN ENGINEER AND THE OTHER IS NOT SIGNED BY
 ANYONE??? PLEASE ADVISE WHY?
  
 END OF COMMENTS.
  