| 2019-07-10 07:19:31 | 7/10/19 DENIED | | | | | | THE GENERATOR SHALL BE ONE FOOT SIX INCHES (1?-6?) FROM | | | THE HOUSE, FIVE (5?-0?) FROM THE PROPERTY LINE, EXHAUST | | | SHALL BE TEN (10?-0?) FROM ANY OPENING UNLESS OTHERWISE | | | STATED IN THE MANUFACTURES SPECIFICATION INSTRUCTIONS. | | | | | | SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE | | | APPLIANCE. COMPLY WITH 2017 FBC FUEL GAS TABLE 402.4 | | | (28) OR 2017 FBC FUEL GAS RES.TABLE G2413.4 (12) | | | SCHEDULE 40 METALLIC PIPE FOR THE PROPER PIPE SIZE AND | | | BTU LOAD. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION | | | | | | ATELYO BELISLE | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6695 | | | |
|