| 2019-07-09 07:00:33 | 7/9/19 DENIED | | | THE GENERATOR SHALL BE ONE FOOT SIX INCHES (1?-6?) FROM | | | THE HOUSE, FIVE (5?-0?) FROM THE PROPERTY LINE, EXHAUST | | | SHALL BE TEN (10?-0?) FROM ANY OPENING UNLESS OTHERWISE | | | STATED IN THE MANUFACTURES SPECIFICATION INSTRUCTIONS. | | | | | | A PORTION OF SHEET 8 IS ILLEGIBLE. SUBMIT TWO COPIES OF | | | CLEAR AND LEGIBLE PLANS FOR REVIEW. WPB AMENDMENTS TO | | | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. | | | | | | SIGNATURE (OR SEAL, OR TITLE BLOCK, OR ALL THREE) ARE | | | NOT IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE | | | 61G15-23.001, FLORIDA STATUTE 471. SUBMIT ORRIGINAL | | | COPIES | | | | | | SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE | | | LENGTH OF ALL CUT SECTIONS OF PIPE, SURVEY INDICATES A | | | DIFFERENT LENGTH OF GAS LINE FROM TANK TO GENERATOR. | | | PLEASE CLARIFY PER 2017 FBC FUEL GAS, SECS. 402.4.1, | | | 402.4.2 | | | | | | CLARIFY BTU LOAD, SPECS SHOW 127K BTU @ FULL LOAD. | | | PLANS CALL FOR 330K BTU. PLEASE CLARIFY | | | | | | ATELYO BELISLE | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6695 | | | | | | |
|