| 2020-02-10 18:23:57 | 3RD REVIEW:.19070244 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | MED GAS COMMENTS: |
| | |
| | 1. PLEASE PLACE NOTE ON PLAN THE CONTRACTOR AND ANYONE |
| | INSTALLING MED GAS PIPING SHALL BE MED GAS CERTIFIED. |
| | INSTALLERS SHALL PROVIDED PROOF FOR PERMIT ISSUE AND ON |
| | JOBSITE FOR INSPECTORS APPROVAL . PER FAC 61G4-15.031 |
| | |
| | 2. PROVIDE NOTE ON PLAN MED GAS SHALL COMPLY WITH NFPA |
| | 99 |
| | |
| | 3. PROVIDE MANUFACTURE SPECIFICATION AND INSTILLATION |
| | GUIDE FOR THE NEW VACUUM PUMP AND AIR COMPRESSOR. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 4. SHT. P3 KEY NOTE A REFERENCES SHT P6 BUT P6 HAS NOT |
| | BEEN UPLOADED PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 5. WHAT TYPE OF PIPING IS BEING USED FOR THE COMPRESSED |
| | AIR LINES. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 6. SHT P3 UNDER PLUMBING KEYNOTES ( DENTAL) REFERENCES |
| | DENTAL DRAWINGS THEY HAVE NOT BEEN DOWNLOADED PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | END OF COMMENTS |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |