| 2020-01-06 17:30:43 | 3RD REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19070244 |
| | 1/6/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | THE MECHANICAL PLANS WERE APPROVED ON 8/14/19 WITH THE |
| | PROVISOS LISED BELOW. THE REVISED PLAN DATED 9/6/19 TO |
| | ADDRESS THOSE PROVISOS IS NOT IN COMPLIANCE. SEE |
| | PROVISOS LISTED BELOW |
| | |
| | |
| | MECHANICAL PROVISOS: |
| | |
| | THE MECHANICAL PLAN IS APPROVED WITH EXCEPTION- A |
| | REVISION IS REQUIRED TO ADDRESS THESE ISSUES: |
| | |
| | 1) PROVIDE AN INDEPENDENT EXHAUST VENTILATION SYSTEM |
| | FOR THE LAB IF CHEMICAL PROCESSING OR TESTING IS |
| | PERFORMED IN THE ROOM. |
| | |
| | 2) THE POLISH ROOM AND TOILET ROOM EXHAUST DUCTS MUST |
| | BE RUN INDEPENDENTLY FROM INLET TO OUTLET. |
| | |
| | 3) THE TRANSFER DUCT (JUMPER) RETURNING AND |
| | RECIRCULATING AIR FROM THE LAB TO THE CORRIDOR IS NOT |
| | ALLOWED. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |