| Date |
Text |
| 2020-03-06 16:41:37 | 03/05/20 2ND MEDICAL GAS REVISION REVIEW **DENIED** |
| | WITH COMMENTS |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS |
| | |
| | REFERENCE: NFPA 99 2012 EDITION |
| | |
| | 1. EQUIPMENT SPECIFICATIONS DO PROVIDE GENERIC DETAILS |
| | FOR CONNECTIONS, BUT DO NOT ADDRESS THE DISTRIBUTION |
| | AND CONFIGURATIONS OF THIS EQUIPMENT LAY OUT THAT IS |
| | NEEDED TO GUIDE THE CONTRACTOR AND INSTALLERS AS WELL |
| | AS ALLOWING THE INSPECTOR TO INSPECT FOR NFPA 99 |
| | COMPLIANCE AND TO CONFIRM THAT THE INSTALLATION |
| | CONFORMS TO THE DESIGNER?S INTENT, PROVIDE DETAILS ON |
| | THE PLAN THAT CLEARLY INDICATE THE MANIFOLDS AND PIPING |
| | DISTRIBUTION AND CONFIGURATIONS REQUIRED FOR A COMPLETE |
| | INSTALLATION. THIS INCLUDES A RISER DIAGRAMS FOR ALL |
| | THE MEDICAL GAS PIPING TO BE INSTALLED. PROVIDE |
| | ISOMETRIC DRAWING FOR MED GAS INCLUDING VACUUM EXHAUST |
| | PER THE WPB AMENDMENTS TO FBC 107.3.5.1.3(13). |
| | |
| | 2. ALL WATER TUBES MEDICAL GAS SHALL BE IN ACCORDANCE |
| | WITH NFPA 99 2012 SECTION 5.3.7.2.1. WITH ASTM B 819, |
| | STANDARD SPECIFICATION FOR SEAMLESS COPPER. |
| | |
| | 3. THERE ARE 2 P-3 SHEETS WHICH ON HAS A REVISION DATE |
| | SO PLEASE DELETE THE ONE NOT NEEDED PER THE WPB AMEND |
| | TO FBC 107.2.1. |
| | |
| | 4. PLEASE PROVIDE SPECIFICATION FOR VACUUM PUMP AND FOR |
| | AIR COMPRESSOR SHOWING COMPLIANCE PER THE WPB |
| | AMENDMENTS TO FBC SEC. 107.2.1. |
| | |
| | 5. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTALLATION |
| | GUIDES FOR ALL MED GAS EQUIPMENT INCLUDING THE DENTAL |
| | CHAIRS, TANKS AND VALVES PER THE WPB AMEND TO FBC |
| | 107.2.1. |
| | |
| | 6. THE AREA(S) HOUSING THE VACUUM PUMP AND AIR |
| | COMPRESSOR SHALL BE VENTILATED PER NFPA 99 SECS. |
| | 5.1.3.3.3.3, 5.1.3.6.3.1, 5.1.3.7.1.1. |
| | |
| | 7. PIPING SYSTEMS FOR CATEGORY 3 GASES SHALL NOT BE |
| | USED AS GROUNDING ELECTRODES PER THE NFPA 99 2012 SEC. |
| | 5.3.13.2.2. |
| | |
| | 8. ALL DOCUMENTATION PERTAINING TO INSPECTIONS AND |
| | TESTING SHALL BE MAINTAINED ON-SITE PER THE NFPA 99 |
| | 2012 SEC. 5.3.9.1.5. |
| | |
| | 9. PROVIDE A DETAIL FOR RESTRAINTS ON THE OXYGEN TANK |
| | INCLUDING WALL ANCHORAGE PER THE WPB AMEND TO FBC |
| | 107.2.1. |
| | |
| | 10. A SEPARATE PERMIT IS REQUIRED FOR MED GAS PER THE |
| | 2017 WPB A TO FBC 107.5. |
| | |
| | 11. CLEARLY SHOW THE TERMINATION POINTE OF THE VACUUM |
| | EXHAUST AND RELIEF PIPING ON THE ROOF PLAN, IT SHALL BE |
| | DISCHARGED ABOVE ROOF IN A SEPARATE VENT PER THE NFPA |
| | 99 2012 SEC. 5.3.8.3.11. (1). |
| | |
| | 12. PLEASE STATE ON THE PLAN WHAT CATEGORY THE MED GAS |
| | SYSTEM IS DESIGNED TO BE PER THE NFPA 99 CHAPTER 4, |
| | CATEGORY 3. |
| | |
| | 13. PROVIDE COMPLETED INSTALLATION MANUALS FOR ALL NEW |
| | MED GAS EQUIPMENT IN DETAIL PER THE 2017 WPB A TO |
| | SECTION FBC 107.3.5. |
| | |
| | 14. NOTE ON THE PLAN THE NUMBER AND SIZE OF TANKS PER |
| | THE WPB AMEND TO FBC 107.2.1. |
| | |
| | 15. PLEASE PROVIDE A LEGEND FOR ALL GAS VALVES PER THE |
| | WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 16. PLEASE PROVIDE DETAIL HOW PIPING IS GOING TO BE |
| | SUPPORTED IN ACCORDANCE WITH NFPA 2012 5.3.7.3.3 PIPE |
| | SUPPORT. PIPE SUPPORT SHALL BE IN ACCORDANCE. |
| | |
| | 17. FILTER MUST COMPLY WITH NSF 42 PLEASE SUBMIT |
| | MANUFACTURES SPECIFICATION FOR COMPLIANCE PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 18. PLEASE PROVIDE HOW WARNING SYSTEM WILL ABIDE PER |
| | THE 5.3.6.22.1 WARNING SYSTEMS FOR MEDICAL GAS SYSTEMS. |
| | |
| | 19. PLEASE PROVIDE HOW PIPE IS GOING TO BE LABELED PER |
| | THE 2012 NFPA 5.3.11.1.4 (1) AT INTERVALS OF NOT MORE |
| | THAN 6.1 M (20 FT). |
| | |
| | 20. PROVIDE PIPING DETAIL OF CONTROL VALVES AND TANK |
| | MANIFOLD ALSO DETAIL OF HOW TANK IS SECURED PER WPB |
| | AMEND TO FBC 107.2.1 AND NFPA 99. |
| | |
| | 21. PLEASE SHOW WHERE EMERGENCY VALVE IS LOCATED AND |
| | LABELED PER THE 2012 NFPA 5.3.6.19.3. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM |
| | [email protected] |
| | 561-701-6437 |
| | |