Plan Review Notes
Plan Review Notes For Permit 19070230
Permit Number 19070230
Review Stop P
Sequence Number 1
Notes
Date Text
2019-07-19 06:29:22SEE 2ND REVIEW PLUMBING STOP
2019-07-09 06:11:08PLUMBING 1ST REVIEW**DENIED**
  
 1) PERSON DESIGNING PLAN SHALL TAKE RESPONSIBILITY BY
 SIGNING PLAN. FS 471, 481, 489
  
 2) PROVIDE FULL FLOOR PLAN SHOWING LOCATIONS OF
 BATHROOMS. FBC 107.3.5
  
 3) PROVIDE SHOWER DETAIL SHOWING WHAT MATERIAL IS BEING
 USED AND 2% PRE-SLOPE. FBC 107.2.1
  
 4) WITH THE REMOVAL AND CAPPING OF THE EXISTING SHOWING
 AND THE CONVERSION OF THE TUB TO SHOWER PROVIDE FIRE
 STOPPING DETAIL SHOWING HOW YOU INTEND ON MAINTAINING
 THE CURRENT LEVEL OF PROTECTION. FBC 107.2.1
  
 5) PLUMBING PERMIT REQUIRED. FBC 105.1
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR