| Plan Review Notes For Permit 19070225 |
| Permit Number |
19070225 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-07-03 14:04:40 | 7/3/2019 1ST PLUMBING/BACKFLOW REVIEW **DENIED** WITH | | | COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. THIS BACKFLOW IS NOT A LEAD-FREE DEVICE WHICH IS | | | REQUIRED BY THE CITY OF WEST PALM BEACH UTILITY | | | DEPARTMENT. YOU CAN REFER TO THEIR CROSS CONNECTION | | | MANUAL IN THE CITY WEB SITE HTTP://WPB.ORG/DEPARTMENTS/ | | | PUBLIC-UTILITIES/FORMS-PUBLICATIONS/BACKFLOW-CROSS-CONN | | | ECTION-CONTROL-MANUAL FOR MORE INFORMATION. THE 975XL | | | WATKINS MODEL IS NOT LEAD-FREE AS THE 975XL2 IS SO | | | PLEASE RESUBMIT SPECS FOR IT. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | | | | ATELYO BELISLE | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | 561-805-6695 | | | |
|