| 2020-01-28 14:09:00 | 1) THE GAS PLAN NOTES AN EXISTING LP UNDERGROUND TANK |
| | BUT TANK SPECIFICATIONS/DETAILS HAVE BEEN UPLOADED. IF |
| | THIS IS AN EXISTING TANK WHY ARE DETAILS FOR A NEW TANK |
| | BEING SUBMITTED? IF THESE DETAILS DO NOT APPLY THEN |
| | REMOVE THEM FROM THE SUBMITTAL. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 2) TWO DIFFERENT MANUFACTURER'S SPECIFICATIONS HAVE |
| | BEEN SUBMITTED FOR THE FIRST AND SECOND STAGE |
| | REGULATORS. WHICH ONES ARE BEING INSTALLED? REMOVE THE |
| | DOCUMENTS FROM THIS SUBMITTAL THAT DO NOT APPLY.WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 3) THE SUBMITTED LINE DIAGRAM NOTES THE BTU LOAD OF THE |
| | BBQ AS 35,000 BUT THE MANUFACTURER'S SPECIFICATIONS |
| | SHOWS BTU VALUES OF 62,000, 89,000 AND 118,000. |
| | IDENTIFY THE MODEL OF THE BBQ BEING INSTALLED AND THE |
| | CORRECT BTU LOAD. 2017 FBC-RES. SEC. G2413.3, G2413.4 |
| | AND TABLES G2413.4 (1 ) THROUGH G2413.4 (21). |
| | 4) THE MANUFACTURER'S SPECIFICATIONS FOR THE MOSQUITO |
| | MAGNET SPECIFY THAT THE UNIT SHOULD BE CONNECTED TO A |
| | MAXIMUM 20 LB. LP GAS CYLINDER/CONTAINER. I CONTACTED |
| | THE MANUFACTURER AND SPOKE TO ONE OF THEIR SERVICE |
| | REPRESENTATIVES WHO EXPLAINED THAT THIS UNIT IS NOT |
| | RECOMMENDED TO BE CONNECTED TO A CYLINDER LARGER THAN |
| | 20 LBS. BECAUSE IT WAS NOT TESTED IN THAT MANNER. |
| | THEREFORE, THIS UNIT IS NOT PERMITTED TO BE CONNECTED |
| | TO THIS GAS SYSTEM. |
| | 5) A GAS SIZING TABLE FOR LOW PRESSURE PE PIPE HAS BEEN |
| | SUBMITTED BUT THE LINE DIAGRAM SHOWS ALL THE PE PIPING |
| | BEING UNDER AN ELEVATED PRESSURE . CLARIFY. |
| | 6) SHOW THE DISTANCE FROM THE MP REGULATORS TO ALL THE |
| | APPLIANCES. 2017 FBC-RES. SEC. G 2413.4.1, G2413.4.2. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |