Plan Review Notes
Plan Review Notes For Permit 19070210
Permit Number 19070210
Review Stop G
Sequence Number 3
Notes
Date Text
2020-01-28 14:09:001) THE GAS PLAN NOTES AN EXISTING LP UNDERGROUND TANK
 BUT TANK SPECIFICATIONS/DETAILS HAVE BEEN UPLOADED. IF
 THIS IS AN EXISTING TANK WHY ARE DETAILS FOR A NEW TANK
 BEING SUBMITTED? IF THESE DETAILS DO NOT APPLY THEN
 REMOVE THEM FROM THE SUBMITTAL. WPB AMEND. TO FBC SEC.
 107.2.1.
 2) TWO DIFFERENT MANUFACTURER'S SPECIFICATIONS HAVE
 BEEN SUBMITTED FOR THE FIRST AND SECOND STAGE
 REGULATORS. WHICH ONES ARE BEING INSTALLED? REMOVE THE
 DOCUMENTS FROM THIS SUBMITTAL THAT DO NOT APPLY.WPB
 AMEND. TO FBC SEC. 107.2.1.
 3) THE SUBMITTED LINE DIAGRAM NOTES THE BTU LOAD OF THE
 BBQ AS 35,000 BUT THE MANUFACTURER'S SPECIFICATIONS
 SHOWS BTU VALUES OF 62,000, 89,000 AND 118,000.
 IDENTIFY THE MODEL OF THE BBQ BEING INSTALLED AND THE
 CORRECT BTU LOAD. 2017 FBC-RES. SEC. G2413.3, G2413.4
 AND TABLES G2413.4 (1 ) THROUGH G2413.4 (21).
 4) THE MANUFACTURER'S SPECIFICATIONS FOR THE MOSQUITO
 MAGNET SPECIFY THAT THE UNIT SHOULD BE CONNECTED TO A
 MAXIMUM 20 LB. LP GAS CYLINDER/CONTAINER. I CONTACTED
 THE MANUFACTURER AND SPOKE TO ONE OF THEIR SERVICE
 REPRESENTATIVES WHO EXPLAINED THAT THIS UNIT IS NOT
 RECOMMENDED TO BE CONNECTED TO A CYLINDER LARGER THAN
 20 LBS. BECAUSE IT WAS NOT TESTED IN THAT MANNER.
 THEREFORE, THIS UNIT IS NOT PERMITTED TO BE CONNECTED
 TO THIS GAS SYSTEM.
 5) A GAS SIZING TABLE FOR LOW PRESSURE PE PIPE HAS BEEN
 SUBMITTED BUT THE LINE DIAGRAM SHOWS ALL THE PE PIPING
 BEING UNDER AN ELEVATED PRESSURE . CLARIFY.
 6) SHOW THE DISTANCE FROM THE MP REGULATORS TO ALL THE
 APPLIANCES. 2017 FBC-RES. SEC. G 2413.4.1, G2413.4.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  