Plan Review Notes
Plan Review Notes For Permit 19070184
Permit Number 19070184
Review Stop B
Sequence Number 1
Notes
Date Text
2019-07-12 15:24:42BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 1901
 REVIEWED: JULY 12, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) 109.3 FBC[AMENDED] PROVIDE COPY OF PROPOSAL WITH
 CONTRACTOR TO SHOW WORK VALUE EQUAL TO THE AMOUNT SHOWN
 ON PERMIT APPLICATION, OR ADJUST VALUE TO MATCH ACTUAL
 COST OF WORK.
 - THE VALUE SEEMS LOW FOR THE AMOUNT OF SLIDERS
 INSTALLED. WAS THIS INSTALLED BT A CONTRACTOR?
 - THE VALUE OF WORK SHOULD BE EQUAL TO WHAT A
 CONTRACTOR WOULD CHARGE FOR TIME, MATERIALS AND
 OVERHEAD.
 - IF THIS WAS OWNER BUILDER THAN AN OWNER BUILDER
 AFFIDAVIT NEEDS TO BE FILLED OUT AND SIGNED HERE AT THE
 BUIDING DEPARTMENT BY THE OWNER.
 THE FORM CAN BE DOWNLOADED FROM. HTTPS://WWW.WPB.ORG/DE
 PARTMENTS/DEVELOPMENT-SERVICES/FORMS/BUILDING-PERMIT-FO
 RMS
  
 2) 609.7.2.1 FBC[R] MASONRY, CONCRETE OR OTHER
 STRUCTURAL SUBSTRATE. WHERE THE WOOD SHIM OR BUCK
 THICKNESS IS LESS THAN 11/2 INCHES (38 MM), WINDOW AND
 GLASS DOOR ASSEMBLIES SHALL BE ANCHORED THROUGH THE
 JAMB, OR BY JAMB CLIP AND ANCHORS SHALL BE EMBEDDED
 DIRECTLY INTO THE MASONRY, CONCRETE OR OTHER
 SUBSTANTIAL SUBSTRATE MATERIAL. ANCHORS SHALL
 ADEQUATELY TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME
 INTO THE ROUGH OPENING SUBSTRATE [SEE FIGURES
 R609.7.2(1) AND R6097.2(2)].
 - PROVIDE WINDOW BUCK DETAIL.
  
 3) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR
 FIXED WINDOWS ABOVE SLIDERS AND WINDOW MULL BETWEEN THE
 FIXED WINDOWS.
 - PLEASE PROVIDE TWO COPIES EACH NEW PRODUCT APPROVAL
 AND ONE COPY ADDITIONAL FOR PRODUCT APPROVALS ALREADY
 SUBMITTED AS ONLY ONE SET WAS TURNED IN WITH THE
 PERMIT.
  
 4) DESIGN DATA:
 A. RISK CATEGORY = ___(II)
 B. EXPOSURE CATEGORY = ___(B,C OR D)
 C. BUILDING CLASSIFICATION = __________(ENCLOSED)
 D. MEAN BLDG. HGT. = ___FT. ___IN.(THIS WILL BE THE
 HEIGHT MEASURED FROM THE GROUND TO IN BETWEEN EAVE AND
 ROOF PEAK, OR THE ROOF DECK ABOVE)
 E. WIND SPEED V ULT = _____(170)
 F. WIND SPEED V ASD = _____(132)
 COMPONANT & CLADDING:
 FBC TABLE 301.2(2) FBC[R]
 DESIGN PRESSURE = +___ & -___
 301.2(3) FBC[R] CHECK EXPOSURE AND M.R.H. TO DETERMINE
 IF ADJUSTMENT FACTOR NEEDED.
 MULTIPLE DESIGN PRESSURES BY THE ADJUSTMENT FACTOR IF <
 OR > 1.00
  
 5) 107.5.3 FBC[AMENDED] OPENING SCHEDULE:
 PROVIDE OPENEING SIZE AND PRESSURE ON EACH WINDOW/DOOR.
 INDICATE IF THE OPENING IS IN THE INTERIOR OR EXTERIOR
 ZONE.
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  