Plan Review Notes
Plan Review Notes For Permit 19070181
Permit Number 19070181
Review Stop G
Sequence Number 2
Notes
Date Text
2019-08-02 07:00:591) THE GAS DRAWING THAT HAS BEEN SUBMITTED NOTES ALL
 PIPING TO BE 1/2" GALVANIZED YET YOU HAVE SUBMITTED A
 SIZING TABLE FOR POLYETHYLENE PIPE. CLARIFY. SUBMIT TWO
 COPIES OF THE APPLICABLE GAS SIZING TABLES FOR THIS
 INSTALLATION.
 2) YOU HAVE SUBMITTED TWO SHEETS OF THE MANUFACTURER'S
 SPECIFICATIONS AND NOTHING ELSE FOR THE REGULATORS.
 SUBMIT MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON THE
 SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING
 INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR
 CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR.2017
 FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  