| Plan Review Notes For Permit 19070181 |
| Permit Number |
19070181 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-08-02 07:00:59 | 1) THE GAS DRAWING THAT HAS BEEN SUBMITTED NOTES ALL | | | PIPING TO BE 1/2" GALVANIZED YET YOU HAVE SUBMITTED A | | | SIZING TABLE FOR POLYETHYLENE PIPE. CLARIFY. SUBMIT TWO | | | COPIES OF THE APPLICABLE GAS SIZING TABLES FOR THIS | | | INSTALLATION. | | | 2) YOU HAVE SUBMITTED TWO SHEETS OF THE MANUFACTURER'S | | | SPECIFICATIONS AND NOTHING ELSE FOR THE REGULATORS. | | | SUBMIT MANUFACTURER'S SPECIFICATIONS AND INSTALLATION | | | INSTRUCTIONS FOR THE PRESSURE REGULATORS. REGULATORS | | | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE | | | APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON THE | | | SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING | | | INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR | | | CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR.2017 | | | FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | | | | |
|