Plan Review Notes
Plan Review Notes For Permit 19070181
Permit Number 19070181
Review Stop G
Sequence Number 1
Notes
Date Text
2019-07-13 05:55:117/13/19 DENIED
  
 SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2017 FBC FUEL GAS TABLE 402.4
 (28) OR 2017 FBC FUEL GAS RES.TABLE G2413.4 (12)
 SCHEDULE 40 METALLIC PIPE FOR THE PROPER PIPE SIZE AND
 BTU LOAD.
  
 PLEASE INDICATE THE BTU LOAD FOR THE OPTIONAL POOL
 HEATER AND GRILL.
  
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  