| Notes |
| Date |
Text |
| 2019-07-13 05:55:11 | 7/13/19 DENIED | | | | | | SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE | | | APPLIANCE. COMPLY WITH 2017 FBC FUEL GAS TABLE 402.4 | | | (28) OR 2017 FBC FUEL GAS RES.TABLE G2413.4 (12) | | | SCHEDULE 40 METALLIC PIPE FOR THE PROPER PIPE SIZE AND | | | BTU LOAD. | | | | | | PLEASE INDICATE THE BTU LOAD FOR THE OPTIONAL POOL | | | HEATER AND GRILL. | | | | | | | | | ATELYO BELISLE | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6695 | | | |
|