| 2019-07-16 15:38:05 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19070169 |
| | REVIEWED: JULY 16, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | |
| | 1) 1004.1 FBC[B]DESIGN OCCUPANT LOAD. IN DETERMINING |
| | MEANS OF EGRESS REQUIREMENTS, THE NUMBER OF OCCUPANTS |
| | FOR WHOM MEANS OF EGRESS FACILITIES ARE PROVIDED SHALL |
| | BE DETERMINED IN ACCORDANCE WITH THIS SECTION. |
| | -PLEASE PROVIDE AREA, OCCUPANCY AND OCCUPANT LOAD FOR |
| | THE EXISTING SPACE LABELED MID FLORIDA ARMORED SPACE. |
| | STORAGE AREA CAN USE STORAGE OCCUPANY FOR OCCUPANT |
| | LOAD. |
| | -IF THE OCCUPACY EXCEEDS 49 THAN 2 EXITS ARE REQUIRED |
| | (SEE COMMENT 2) |
| | |
| | 2) 1006.1 FBC[B]GENERAL. THE NUMBER OF EXITS OR EXIT |
| | ACCESS DOORWAYS REQUIRED WITHIN THE MEANS OF EGRESS |
| | SYSTEM SHALL COMPLY WITH THE PROVISIONS OF SECTION |
| | 1006.2 |
| | -THE LIFE SAFETY PLANS SHOWS ADDITIONAL EXIT THROUGH |
| | THE OTHER TENANT SPACE. IT APPEARS THAT BATHROOMS ARE |
| | SHARED, BUT THE OTHER SPACE THAT IS HATCHED IS OPEN AND |
| | WOULDN?T APPEAR TO BE A MEANS OF EGRESS. |
| | -IS THE BUILDING SPRINKLED? |
| | PLEASE ADD TO DATA TABLE SO THE MAXIMUM COMMON PATH OF |
| | TRAVEL CAN BE ESTABLISHED. |
| | ACCORDING TO A-2 BUILDING ANALYSIS COMMON PATH OF |
| | TRAVEL IS 75 FEET AND MAX DEAD END CORRIDOR IS 20 FEET. |
| | THE DRAWING SHOWS 100 FEET FROM OFFICE 6 AND DEAD |
| | COORIDOR IS OVER 20 FEET. |
| | |
| | NOTES: |
| | WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |