| Plan Review Notes For Permit 19070147 |
| Permit Number |
19070147 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2020-03-24 11:58:34 | REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CORRECTIONS NEEDED - | | | 1) BUILDING CODE VERSION SHOWN ON COVER PAGE (001 | | | CS-000) IS INCORRECT - SHOULD BE 2017 FBC | | | 2) PLEASE PROVIDE PRODUCT APPROVALS FOR THE NEW | | | EXTERIOR DOORS. FBC WPB AMENDMENTS 107.3.4.1 | | | 3) PLEASE PROVIDE THE FLOORING SYSTEM ACOUSTICAL | | | TESTING REPORT FOR THE TILE FLOORING AND UNDERLAYMENT | | | BEING USED IN THE UNITS TO COMPLY WITH FBC 1207.3 (IIC) | | | | | | | | | |
|