| 2019-12-02 12:10:13 | PLUMBING 2ND REVIEW**DENIED** |
| | |
| | PLEASE RESPOND TO ALL COMMENTS. YOU CALL OUT SHT. |
| | CS-000 AND A-100 IN YOUR RESPONSE TO COMMENTS BUT NO |
| | NEW SHEETS SUBMITTED. SEE 1ST REVIEW COMMENTS BELOW |
| | |
| | |
| | |
| | PLUMBING 1ST REVIEW**DENIED** |
| | |
| | |
| | 1) SHT. CS-000 STATES BUILDING WAS CONSTRUCTED IN 1998. |
| | BUILDING BUILT AFTER MARCH 13, 1991 SHOULD HAVE BEEN |
| | CONSTRUCTED AND APPEARS BY EXISTING BATHROOM FIXTURE |
| | LAY OUT TO HAVE BEEN UNDER THE FAIR HOUSING MANUAL |
| | (FHA). THE NEW PROPOSED RENOVATIONS SHALL ALSO COMPLY |
| | WITH FHA. THE PROPOSED TUB TO SHOWER CONVERSION WILL |
| | NOT COMPLY AND PROVIDE THE REQUIRED CLEAR FLOOR SPACE |
| | AS TOILETS AND CABINETS SHALL NOT ENCROACH INTO THE |
| | CLEAR FLOOR SPACE. FHA 7.55. PROVIDE |
| | |
| | 2) PROVIDE WHAT DESIGN SPEC ( A OR B) EACH UNIT |
| | CURRENTLY IS. |
| | |
| | 3) PROVIDE CABINET HEIGHT DETAIL SHOWING MAX HEIGHT OF |
| | CABINETS WILL BE 34?. FHA 7.52 |
| | |
| | 4) SHT. CS-000 SHALL REFER TO THE CURRENT CODE AS THE |
| | 2014 5TH ED FLORIDA BUILDING CODE AND FLORIDA |
| | ACCESSIBILITY CODE. FBC 107.1 |
| | |
| | 5) SHT. A-001 DETAIL #2 THE DISTANCE TO THE TOILET |
| | PAPER DISPENSER SHALL BE TO CENTER OF THE 1ST ROLL AND |
| | NOT THE CENTER OF A DOUBLE ROLL UNIT. FBC-ACC 604.7 |
| | |
| | 6) SHT. A-001 DETAIL #5 THE 40? MAX HEIGHT OF THE |
| | MIRROR IS TO THE REFLECTING SURFACE AND NOT THE BOTTOM |
| | EDGE. FBC-ACC 603.3 |
| | |
| | |
| | TIM HUNT |
| | |
| | PLUMBING PLANS EXAMINER |
| | |
| | CITY OF WEST PALM BEACH |
| | |
| | 561-248-2703 |
| | |
| | [email protected] |
| | |