| Date |
Text |
| 2019-11-06 10:23:10 | FIRE COMMENTS NOT SPECIFICALLY ADDRESSED AND REINSERTED |
| | WITH ADDITIONAL COMMENTS BELOW: |
| | |
| | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | THERE IS INSUFFICIENT INFORMATION PROVIDED TO CONDUCT A |
| | DETAILED LIFE SAFETY REVIEW. |
| | |
| | |
| | 1) SHEET A 101 - FIRE MISUNDERSTOOD THE WORDING OF THE |
| | # 26 NOTE - COMPLIED. |
| | |
| | |
| | |
| | 2) NO LIFE SAFETY SHEETS - IS THE PROPOSED PROJECT |
| | BEING CONDUCTED WITH THE BUILDING OCCUPIED WITH GUESTS |
| | ON THE SAME OR ANY FLOORS. |
| | |
| | PLEASE CLARIFY AND PROVIDE DETAILS OF PHASING OR |
| | SEQUENCES OF WORK. |
| | |
| | NOT COMPLIED, PLEASE ADDRESS. |
| | |
| | |
| | 2A) THERE ARE INDICATIONS OF FLOORS, WALLS, STAIRS, |
| | CEILINGS, BEING WORKED ON. |
| | |
| | HOW WILL EXITING AND MAINTNENCE FOR ALL LIFE SAFETY |
| | SYSTEM BEING ACCOMPLISHED WHILE BEING OCCUPIED? |
| | |
| | A DETAILED LIFE SAFETY PLAN FOR EACH FLOOR IS REQUIRED |
| | INDICATING HOW ALL LIFE SAFETY SYSTEMS, EXITS, TRAVEL |
| | DISTANCES, COMMON PATHS OT TRAVEL AND EXIT DISCHARGES |
| | WILL BE MAINTAINED. |
| | |
| | |
| | NOT COMPLIED, PLEASE ADDRESS |
| | |
| | |
| | |
| | 3) FIRE ALARM AND FIRE SPRINKLER - THE PROPOSED WORK |
| | MAY AFFECT FA & FS EQUIPMENT, DEVICES, HEADS, FUNCTION, |
| | ETC. |
| | |
| | ANY WORK ON THE FA & FS SYSTEM SHALL BE DONE UNDER |
| | SEPARATE PERMIST AND SHOP DRAWINGS BY CERTIFIED |
| | CONTRACTORS. |
| | |
| | THE FA & FS SYSTEMS SHALL BE MAINTAINED THROUGHOUT DEMO |
| | AND CONSTRUCTION. |
| | |
| | PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE AN |
| | APPLICABLE NOTE ON THE LIFE SAFETY PLAN SHEETS. |
| | |
| | |
| | NOT COMPLIED, PLEASE ADDRESS |
| | |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | NOT COMPLIED, PLEASE ADDRESS |
| | |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | STATEMENT RESUBMITTED |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |