| 2019-11-26 14:13:21 | 2ND REVIEW NOVEMBER 26, 2019 |
| | |
| | I SEE A COMMENT RESPONSE SHEET THAT STATES VARIOUS |
| | SHEETS REPLACED, BUT THEY WERE NOT UPLOADED INTO |
| | PROJECTDOX. |
| | PLEASE UPLOAD THE NEW SHEETS AND I CAN COMPLETE MY |
| | REVIEW. |
| | |
| | |
| | |
| | |
| | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19070147 |
| | REVIEWED: AUGUST 12, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | |
| | 1) 107.5.3 FBC[AMENDED] CODE EDITION. |
| | PLEASE UPDATE SHEET CS-000 WHERE IS STATES FBC 2014 5TH |
| | EDITION TO READ FLORIDA BUILDING CODE 6TH EDITION |
| | (2017) AND AMENDMENTS ARE 2017 AS WELL. |
| | |
| | 2) 301.1 FBC[EXISTING] GENERAL. THE REPAIR, ALTERATION, |
| | CHANGE OF OCCUPANCY, ADDITION OR RELOCATION OF ALL |
| | EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS |
| | LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED |
| | BY THE APPLICANT. SECTIONS 301.1.1 THROUGH 301.1.3 |
| | SHALL NOT BE APPLIED IN COMBINATION WITH EACH OTHER. |
| | A) 301.1.1 FBC[EXISTING] PRESCRIPTIVE COMPLIANCE |
| | METHOD. REPAIRS, ALTERATIONS, ADDITIONS AND CHANGES OF |
| | OCCUPANCY COMPLYING WITH CHAPTER 4 OF THIS CODE IN |
| | BUILDINGS COMPLYING WITH THE FLORIDA FIRE PREVENTION |
| | CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE |
| | PROVISIONS OF THIS CODE. |
| | B) 301.1.2 FBC[EXISTING] WORK AREA COMPLIANCE METHOD. |
| | REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY |
| | AND RELOCATED BUILDINGS COMPLYING WITH THE APPLICABLE |
| | REQUIREMENTS OF CHAPTERS 5 THROUGH 13 OF THIS CODE |
| | SHALL BE CONSIDERED IN COMPLIANCE WITH THE PROVISIONS |
| | OF THIS CODE. |
| | C) 301.1.3 FBC[EXISTING] PERFORMANCE COMPLIANCE METHOD. |
| | REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY |
| | AND RELOCATED BUILDINGS COMPLYING WITH CHAPTER 14 OF |
| | THIS CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE |
| | PROVISIONS OF THIS CODE. |
| | - WHICH METHOD IS BEING USED FOR COMPLIANCE? |
| | (PRESCRIPTIVE,WORK AREA OR PERFORMANCE) |
| | |
| | 3) 501 FBC[EXISTING] IF WORK AREA PLEASE STATE THE |
| | LEVEL OF ALTERATION FOR WORK BEING PERFORMED. |
| | A) LEVEL 1 ALTERATION |
| | B) LEVEL 2 ALTERATION |
| | C) LEVEL 3 ALTERATION |
| | |
| | 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR |
| | EXTERIOR DOORS AND SIDE PANELS AS APPLICABLE. |
| | |
| | 4) 107.2.1.2 FBC[AMENDED] PROVIDE STAIRCASE RAILS |
| | ENGINEERING, OR INDICATE THAT IT WILL BE DEFERRED. |
| | |
| | 5) 1207.2 FBC[B] PLEASE ADVISE ,VIA EMAIL, WHAT |
| | FLOORING UNDERLAYMENT IS PROPOSED? IF THE UNDERLAYMENT |
| | PRODUCT PROPOSED IS NOT ONE FOR WHICH WE HAVE TEST |
| | REPORTS ON FILE, THE FOLLOWING REPORTS WILL BE |
| | REQUIRED: |
| | 1207.2 FBC[B] AIR-BORNE SOUND. WALLS, PARTITIONS AND |
| | FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS AND |
| | SLEEPING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS OF |
| | NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED, |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E90. |
| | 1207.3 FBC[B] STRUCTURE-BORNE SOUND. FLOOR/CEILING |
| | ASSEMBLIES BETWEEN DWELLING UNITS AND SLEEPING UNITS OR |
| | BETWEEN A DWELLING UNIT OR SLEEPING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS RATING OF NOT LESS THAN 50, OR |
| | NOT LESS THAN 45 IF FIELD TESTED, WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E492. |
| | 603.1 FBC[B] ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. |
| | 804.1 FBC[B] GENERAL. INTERIOR FLOOR FINISH AND FLOOR |
| | COVERING MATERIALS SHALL COMPLY WITH SECTIONS 804.2 |
| | THROUGH 804.4.2. EXCEPTION: FLOOR FINISHES AND |
| | COVERINGS OF A TRADITIONAL TYPE, SUCH AS WOOD, VINYL, |
| | LINOLEUM OR TERRAZZO, AND RESILIENT FLOOR COVERING |
| | MATERIALS THAT ARE NOT COMPRISED OF FIBERS. |
| | -THIS WOULD APPLY TO SECOND AND THIRD FLOORS IN THE |
| | SLEEPING UNITS ONLY. |
| | |
| | 6) 806.1 FBC[B] GENERAL. COMBUSTIBLE DECORATIVE |
| | MATERIALS, OTHER THAN DECORATIVE VEGETATION, SHALL |
| | COMPLY WITH SECTIONS 806.2 THROUGH 806.8. [F] 806.2 |
| | NONCOMBUSTIBLE MATERIALS. THE PERMISSIBLE AMOUNT OF |
| | NONCOMBUSTIBLE MATERIALS SHALL NOT BE LIMITED. |
| | -PROVISO: IF WINDOW TREATMENTS FALL UNDER 806.3 THEN |
| | SUBMIT REPORTS TO INSPECTOR PRIOR TO INSTALL. |
| | |
| | 7) PLEASE ADD NOTE TO SHEET SP-100 THAT PARKING LOT |
| | UPGRADES WILL BE DONE UNDER SEPARATE PERMIT. |
| | |
| | 8) 902.1 FBC[A]GENERAL. DINING SURFACES AND WORK |
| | SURFACES SHALL COMPLY WITH 902.2 AND 902.3. 902.3 |
| | HEIGHT. THE TOPS OF DINING SURFACES AND WORK SURFACES |
| | SHALL BE 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865 |
| | MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | -PLEASE SHOW ACCESSIBLE EATING AREAS IN HEARTHROOM |
| | |
| | PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW EACH |
| | COMMENT IS BEING ADDRESSED. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |