| Plan Review Notes For Permit 19070147 |
| Permit Number |
19070147 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-08-19 06:22:28 | PLUMBING 1ST REVIEW**DENIED** | | | | | | 1) SHT. CS-000 STATES BUILDING WAS CONSTRUCTED IN 1998. | | | BUILDING BUILT AFTER MARCH 13, 1991 SHOULD HAVE BEEN | | | CONSTRUCTED AND APPEARS BY EXISTING BATHROOM FIXTURE | | | LAY OUT TO HAVE BEEN UNDER THE FAIR HOUSING MANUAL | | | (FHA). THE NEW PROPOSED RENOVATIONS SHALL ALSO COMPLY | | | WITH FHA. THE PROPOSED TUB TO SHOWER CONVERSION WILL | | | NOT COMPLY AND PROVIDE THE REQUIRED CLEAR FLOOR SPACE | | | AS TOILETS AND CABINETS SHALL NOT ENCROACH INTO THE | | | CLEAR FLOOR SPACE. FHA 7.55. PROVIDE | | | 2) PROVIDE WHAT DESIGN SPEC ( A OR B) EACH UNIT | | | CURRENTLY IS. | | | 3) PROVIDE CABINET HEIGHT DETAIL SHOWING MAX HEIGHT OF | | | CABINETS WILL BE 34?. FHA 7.52 | | | 4) SHT. CS-000 SHALL REFER TO THE CURRENT CODE AS THE | | | 2017 5TH ED FLORIDA BUILDING CODE AND FLORIDA | | | ACCESSIBILITY CODE. FBC 107.1 | | | 5) SHT. A-001 DETAIL #2 THE DISTANCE TO THE TOILET | | | PAPER DISPENSER SHALL BE TO CENTER OF THE 1ST ROLL AND | | | NOT THE CENTER OF A DOUBLE ROLL UNIT. FBC-ACC 604.7 | | | 6) SHT. A-001 DETAIL #5 THE 40? MAX HEIGHT OF THE | | | MIRROR IS TO THE REFLECTING SURFACE AND NOT THE BOTTOM | | | EDGE. FBC-ACC 603.3 | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-248-2703 | | | [email protected] | | | | | | | | | |
|