Plan Review Notes
Plan Review Notes For Permit 19070092
Permit Number 19070092
Review Stop B
Sequence Number 2
Notes
Date Text
2019-07-26 08:55:15REVISION SECOND BUILDING REVIEW CHECKLIST.
 FBC 6TH EDITION (2017).
  
 ORIGINAL COMMENT:
 1- CHECK IN DESK WAS REVISED. PLEASE REVISE HEIGHT OF
 CHECK-IN DESK TO SHOW COMPLIANCE WITH SEC. 904.4
 FBC-ACCESSIBILITY.
  
 RESPONSE:
 PROPOSED REVISED COUNTER SHOWN ON SHEET A4.2 (SHEET 012
 A403 ON DOWNLOADED DIGITAL DRAWING) DOESN'T COMPLY WITH
 SEC. 904.4 FBC-ACCESSIBILITY. THE LENGTH OF THE COUNTER
 DOESN'T COMPLY WITH EITHER SEC. 904.4.1 OR SEC.
 904.4.2. PLEASE REVISE AS REQUIRED. CLEARLY SHOW IF THE
 COUNTER IS FOR PARALLEL APPROACH OR FORWARD APPROACH.
 NOTE: PLEASE REVISE THE EQUIPMENT FLOOR PLAN TO REFLECT
 ANY CHANGES ON THIS COUNTER.
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  