Plan Review Notes
Plan Review Notes For Permit 19070090
Permit Number 19070090
Review Stop M
Sequence Number 2
Notes
Date Text
2019-09-20 12:01:172ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19070090
 9/20/2019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M1: 2ND REQUEST FOR A NOTE ON THE PLAN INDICATING
 SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN HOOD,
 FIRE SUPPRESSION SYSTEM, AND WALK-IN COOLER AND
 FREEZER.
  
 2) M1: THE MAKEUP AIR FOR THE HOOD IS FOR REPLACEMENT
 OF THE THE KITCHEN EXHAUST AIR AND CANNOT BE USED AS
 COMBUSTION AIR FOR THE GAS-FIRED APPLIANCES- SEE
 SECTION 304.9.3 FBC FG. MECHANICAL VENTILATION SYSTEMS
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR IN ADDITION
 TO THE REQUIRED VENTILATION AIR.
  
 3) BASED ON THE ENGINEER'S RESPONSE IN REGARD TO MAKEUP
 AIR TEMPERATURE DIFFERENTIAL (1ST REVIEW COMMENT #5
 PRINTED BELOW), THE SUBMITTED AC CALCULATIONS ARE NOT
 SHOWING THE ADDITIONAL HEAT LOAD FROM THE 10% OF MAKEUP
 AIR CFMS THAT WILL BE DIFFUSED INTO THE SPACE.
  
 5) ADVISORY: THE HOOD IS UNDER SEPARATE PERMIT HOWEVER
 MEETING COMPLIANCE WITH SECTION 508.1.1 MAY REQUIRE
 CHANGES TO THE MAIN HVAC DESIGN. VERIFY THAT THE
 TEMPERATURE DIFFERENTIAL BETWEEN THE EXHAUST HOOD
 MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE DOES
 NOT EXCEED 10 DEGREES F- SECTION 508.1.1 FBC M.
 508.1.1MAKEUP AIR TEMPERATURE. THE TEMPERATURE
 DIFFERENTIAL BETWEEN MAKEUP AIR AND THE AIR IN THE
 CONDITIONED SPACE SHALL NOT EXCEED 10?F (6?C) EXCEPT
 WHERE THE ADDED HEATING AND COOLING LOADS OF THE MAKEUP
 AIR DO NOT EXCEED THE CAPACITY OF THE HVAC SYSTEM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  