| 2019-09-20 12:01:17 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19070090 |
| | 9/20/2019 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) M1: 2ND REQUEST FOR A NOTE ON THE PLAN INDICATING |
| | SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN HOOD, |
| | FIRE SUPPRESSION SYSTEM, AND WALK-IN COOLER AND |
| | FREEZER. |
| | |
| | 2) M1: THE MAKEUP AIR FOR THE HOOD IS FOR REPLACEMENT |
| | OF THE THE KITCHEN EXHAUST AIR AND CANNOT BE USED AS |
| | COMBUSTION AIR FOR THE GAS-FIRED APPLIANCES- SEE |
| | SECTION 304.9.3 FBC FG. MECHANICAL VENTILATION SYSTEMS |
| | SHALL PROVIDE THE SPECIFIED COMBUSTION AIR IN ADDITION |
| | TO THE REQUIRED VENTILATION AIR. |
| | |
| | 3) BASED ON THE ENGINEER'S RESPONSE IN REGARD TO MAKEUP |
| | AIR TEMPERATURE DIFFERENTIAL (1ST REVIEW COMMENT #5 |
| | PRINTED BELOW), THE SUBMITTED AC CALCULATIONS ARE NOT |
| | SHOWING THE ADDITIONAL HEAT LOAD FROM THE 10% OF MAKEUP |
| | AIR CFMS THAT WILL BE DIFFUSED INTO THE SPACE. |
| | |
| | 5) ADVISORY: THE HOOD IS UNDER SEPARATE PERMIT HOWEVER |
| | MEETING COMPLIANCE WITH SECTION 508.1.1 MAY REQUIRE |
| | CHANGES TO THE MAIN HVAC DESIGN. VERIFY THAT THE |
| | TEMPERATURE DIFFERENTIAL BETWEEN THE EXHAUST HOOD |
| | MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE DOES |
| | NOT EXCEED 10 DEGREES F- SECTION 508.1.1 FBC M. |
| | 508.1.1MAKEUP AIR TEMPERATURE. THE TEMPERATURE |
| | DIFFERENTIAL BETWEEN MAKEUP AIR AND THE AIR IN THE |
| | CONDITIONED SPACE SHALL NOT EXCEED 10?F (6?C) EXCEPT |
| | WHERE THE ADDED HEATING AND COOLING LOADS OF THE MAKEUP |
| | AIR DO NOT EXCEED THE CAPACITY OF THE HVAC SYSTEM. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |