| 2019-09-17 10:58:49 | 2ND REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | GAS COMMENTS: | | | | | | 1. SHT. P-3 UNDER GAS PIPING MATERIAL AND CODE TABLE IT | | | REFERENCES ABOVE GROUND IN CRAWL SPACE WILL THE GAS | | | PIPING BE RUNNING IN A CRAWL SPACE PLEASE CLARIFY. PER | | | WPB AMEND TO FBC 107.2.1 | | | | | | 2. YOU ARE LIST TWO TYPES OF PIPING MATERIAL ON THE | | | SIZING TABLE PLEASE LABEL THE GAS PIPING ISOMETRIC WITH | | | TYPE OF MATERIAL FOR PIPING. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | 3. SHT M-1 SHOW LOCATION OF WATER HEATER INTAKE AND | | | EXHAUST WITH DIMENSIONS FROM FRESH AIR INTAKE MIN OF | | | 10'. PER WPB AMEND TO FBC 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|