| 2019-09-25 17:33:21 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | ORIGINAL COMMENT: |
| | 1) THE DEMO FLOOR PLAN AND THE SHEET A1.0 ARCHITECTURAL |
| | FLOOR PLAN SHOW ONE WINDOW PAIN AND EGRESS DOOR |
| | SWAPPING PLACES. THE 2017 WEST PALM BEACH AMENDMENTS TO |
| | THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE |
| | CODE SECTION 104.9.1 USED MATERIALS AND EQUIPMENT. THE |
| | USE OF USED, RECYCLED, OR RECLAIMED MATERIALS WHICH |
| | MEET THE REQUIREMENTS OF THIS CODE FOR NEW MATERIALS IS |
| | PERMITTED. THE MATERIALS AND EQUIPMENT SHALL NOT BE |
| | REUSED UNLESS APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | I HAVE SPOKEN WITH THE BUILDING OFFICIAL ROBERT BROWN |
| | ABOUT THE REUSE OF THE DOOR, FRAME AND GLAZING FOR BOTH |
| | THE DOOR AND SIDE LIGHT. THE BUILDING OFFICIAL IS OK |
| | WITH THE REUSE OF THE PRODUCT AS LONG AS YOU CAN |
| | PROVIDE DOCUMENTATION THAT THE PRODUCT (DOOR & WINDOW |
| | STOREFRONT SYSTEM) WILL MEET TODAY CODE (WIND LOADS) |
| | AND PROVIDE INSTALLATION INSTRUCTIONS FOR THE POSITIVE |
| | AND NEGATIVE PRESSURES THAT WILL OCCUR ON THE |
| | STOREFRONT, FRAMING MEMBERS, GLAZING AND PROVIDE AN |
| | ANCHORING OF SAID SYSTEMS MEETING TODAYS WIND LOADS. |
| | |
| | RESPONSE: |
| | ONLY THE DOOR PRODUCT APPROVAL WAS SUBMITTED. THERE IS |
| | NO PRODUCT APPROVAL SUBMITTED FOR THE FIXED WINDOW. |
| | ALSO, DOOR PRODUCT APPROVAL FL8712-R5 SUBMITTED IS FOR |
| | A DOOR WITH GLAZING THAT HAS NO IMPACT PROTECTION. SEC. |
| | 707.4 FBC-EXISTING BUILDING REQUIRES REPLACEMENT OF |
| | WINDOWS/DOORS TO COMPLY WITH CHAPTER 16 OF THE FLORIDA |
| | BUILDING CODE, BUILDING. THEREFORE, GLAZING OF THE DOOR |
| | REQUIRES IMPACT PROTECTION AS REQUIRED BY SEC. 1609.1.2 |
| | FBC-BUILDING. SHOW COMPLIANCE WITH THE IMPACT |
| | PROTECTION. IF USING HURRICANE SHUTTERS, THEN PROVIDE |
| | SHUTTERS PRODUCT APPROVAL AS REQUIRED BY SEC. |
| | 61G20-3.001 FAC. AND COMPLETE SHUTTERS INSTALLATION |
| | SCHEDULE AS REQUIRED BY CITY POLICY FOR SHUTTERS |
| | INSTALLATION. |
| | |
| | |
| | ORIGINAL COMMENT: |
| | 2) NEW ROOF TOP RTU AND CURB. THE MECHANICAL SHEET M2 |
| | REFERS TO THE ARCHITECTURAL SHEETS FOR THE CURB |
| | MOUNTING DETAILS. THE S1.0 SHEET DOES SHOW HOW TO |
| | RE-ENFORCE THE BAR JOIST AND METAL ROOF DECK BUT THE |
| | PLAN IS SILENT OF THE ATTACHMENT OF THE RTU CURB TO THE |
| | ROOF FRAMING MEMBERS NOR THE RTU UNIT TO THE CURB. |
| | |
| | LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP |
| | EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS, |
| | DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL |
| | AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. |
| | |
| | 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| | LOADS. |
| | |
| | |
| | RESPONSE: |
| | STRUCTURAL PLANS DON'T PROVIDE DETAILS ANS |
| | SPECIFICATIONS FOR THE ATTACHMENT OF THE RTU CURB TO |
| | THE ROOF FRAMING MEMBERS AS REQUESTED. DETAILS |
| | SUBMITTED ON SHEET S1.1 AND S1.2 ARE ONLY THE PRODUCT |
| | APPROVALS FOR ATTACHMENT OF THE MECHANICAL UNIT TO THE |
| | CURB. NOTE ON CURB MOUNT APPLICATIONS CONFIGURATION B |
| | ON PAGE 2 OF FLORIDA PRODUCT APPROVAL FL26981 CLEARLY |
| | STATE THAT "DESIGN & INSTALLATION OF CURB TO JOIST BY |
| | OTHERS PER SITE SPECIFIC CONDITIONS". ENGINEER OF |
| | RECORD TO PROVIDE THESE INFORMATION. SEC. 1603.1 |
| | FBC-BUILDING. |
| | |
| | |
| | |
| | 3) OK. |
| | |
| | 4) OK. |
| | |
| | 5) OK. |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| | COMMENTS, |