| 2019-08-05 11:37:11 | PLUMBING 1ST REVIEW**DENIED**PERMIT # 19070090 |
| | 1-SHT.A0.0 LIST THE 2014 ACCESSIBILITY CODE. CODE IN |
| | PLACE AT THIS TIME IS THE 2017 6TH ED OF THE FLORIDA |
| | ACCESSIBILITY CODE. PLEASE ADDRESS. FBC 107.2.1 |
| | 2-SHT. LSP SHOW?S BOTH TOILET ROOM DOORS SWINGING INTO |
| | THE FIXTURES CLEAR FLOOR SPACE. THIS IS NOT PERMITTED |
| | UNDER FBC-ACC 603.2.3 UNLESS 1 OF THE 2 EXCEPTIONS ARE |
| | MEET COMPLYING WITH 305.3 SHOW AN ADDITIONAL 30?X48? |
| | CLEAR FLOOR SPACE BEYOND THE ARC OF THE DOOR. |
| | 3-SHT B2.0 ACCESSORY SCHEDULE CALLS OUT FOR THE GRAB |
| | BARS MOUNTING TO BE 33?-36? TO THE CENTER. THE |
| | MEASUREMENT SHALL BE TO THE TOP/ GRIPPING SURFACE OF |
| | THE GRAB BAR. FBC-ACC 609.4 |
| | 4- SHT B2.O0 DETAIL #1 SHOWS 1 OF THE 60? TURNING SPACE |
| | ENCROACHING INTO THE WALL. TURNING SPACE SHALL BE A |
| | CLEAR 60?. FBC-ACC 603.2.1, 603.2.2 |
| | 5- UNABLE TO LOCATE THE HI-LOW DRINKING FOUNTAIN ON THE |
| | PLAN. PLEASE PROVIDE AS REQUIRED FBC-PLB 410.3 |
| | 6- PLEASE CLARIFY YOU LIST THE OCCUPANCY AS BUSINESS ON |
| | THE COVER SHEET BUT ON SHT LSD YOU CALL OUT AS |
| | ASSEMBLY. FBC 107.2.1 |
| | 7- PROVIDE TOTAL DEVELOPED LENGTH OF THE HOT WATER LINE |
| | FROM THE WATER HEATER TO THE MOST REMOTE FIXTURE. IF |
| | OVER 50? A RECIRCULATING SYSTEM SHALL BE PROVIDED. |
| | FBC-PLB 607.2 |
| | 8- SHT. P3 UNDER DOMESTIC PIPING NOTE #2 YOU CALL OUT |
| | WATER PIPING AS PEX BUT ALL JOINTS TO BE LEAD FREE 95/5 |
| | SOLDER JOINTS. PLEASE CLARIFY WHAT WATER PIPING SYSTEM |
| | YOU ARE CALLING OUT. FBC 107.2.1 |
| | |
| | TIM HUNT |
| | PLUMBING PLAN REVIEW |