2019-08-05 11:37:11PLUMBING 1ST REVIEW**DENIED**PERMIT # 19070090
 1-SHT.A0.0 LIST THE 2014 ACCESSIBILITY CODE. CODE IN
 PLACE AT THIS TIME IS THE 2017 6TH ED OF THE FLORIDA
 ACCESSIBILITY CODE. PLEASE ADDRESS. FBC 107.2.1
 2-SHT. LSP SHOW?S BOTH TOILET ROOM DOORS SWINGING INTO
 THE FIXTURES CLEAR FLOOR SPACE. THIS IS NOT PERMITTED
 UNDER FBC-ACC 603.2.3 UNLESS 1 OF THE 2 EXCEPTIONS ARE
 MEET COMPLYING WITH 305.3 SHOW AN ADDITIONAL 30?X48?
 CLEAR FLOOR SPACE BEYOND THE ARC OF THE DOOR.
 3-SHT B2.0 ACCESSORY SCHEDULE CALLS OUT FOR THE GRAB
 BARS MOUNTING TO BE 33?-36? TO THE CENTER. THE
 MEASUREMENT SHALL BE TO THE TOP/ GRIPPING SURFACE OF
 THE GRAB BAR. FBC-ACC 609.4
 4- SHT B2.O0 DETAIL #1 SHOWS 1 OF THE 60? TURNING SPACE
 ENCROACHING INTO THE WALL. TURNING SPACE SHALL BE A
 CLEAR 60?. FBC-ACC 603.2.1, 603.2.2
 5- UNABLE TO LOCATE THE HI-LOW DRINKING FOUNTAIN ON THE
 PLAN. PLEASE PROVIDE AS REQUIRED FBC-PLB 410.3
 6- PLEASE CLARIFY YOU LIST THE OCCUPANCY AS BUSINESS ON
 THE COVER SHEET BUT ON SHT LSD YOU CALL OUT AS
 ASSEMBLY. FBC 107.2.1
 7- PROVIDE TOTAL DEVELOPED LENGTH OF THE HOT WATER LINE
 FROM THE WATER HEATER TO THE MOST REMOTE FIXTURE. IF
 OVER 50? A RECIRCULATING SYSTEM SHALL BE PROVIDED.
 FBC-PLB 607.2
 8- SHT. P3 UNDER DOMESTIC PIPING NOTE #2 YOU CALL OUT
 WATER PIPING AS PEX BUT ALL JOINTS TO BE LEAD FREE 95/5
 SOLDER JOINTS. PLEASE CLARIFY WHAT WATER PIPING SYSTEM
 YOU ARE CALLING OUT. FBC 107.2.1
  