Plan Review Notes
Plan Review Notes For Permit 19070090
Permit Number 19070090
Review Stop M
Sequence Number 1
Notes
Date Text
2019-08-09 13:32:291ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19070090
 8/9/2019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR THE
 KITCHEN HOOD, FIRE SUPPRESSION SYSTEM, AND WALK-IN
 COOLER AND FREEZER. PLEASE PLACE A NOTE ON THE PLAN.
  
 2) M1.0: INDICATE HOW COMBUSTION AIR IS BEING PROVIDED
 TO THE NEW GAS COOKING APPLIANCES AND PROVIDE
 CALCULATIONS- SECTION 304.1 FBC-17 FUEL GAS.
  
 3) M1.0: SUBMIT MANUFACTURER?S SPECIFICATIONS (CUT
 SHEETS) FOR THE NEW COOKING APPLIANCES- SECTION 623.1
 FBC-17 FUEL GAS
  
 4) M2.0: GRAVITY OR MOTORIZED SHUTOFF DAMPERS ARE
 REQUIRED FOR THE RTU O/A INTAKES - SECTION C403.2.4.3
 FBC-17 ENERGY CONSERVATION.
  
 5) M1.0: IT APPEARS THE O/A INTAKE FOR RTU-2 IS LOCATED
 WITHIN THE REQUIRED 10? CLEARANCE TO THE EXHAUST VENT-
 SEE SECTION 401.4 FBC M.
  
 5) ADVISORY: THE HOOD IS UNDER SEPARATE PERMIT HOWEVER
 MEETING COMPLIANCE WITH SECTION 508.1.1 MAY REQUIRE
 CHANGES TO THE MAIN HVAC DESIGN. VERIFY THAT THE
 TEMPERATURE DIFFERENTIAL BETWEEN THE EXHAUST HOOD
 MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE DOES
 NOT EXCEED 10 DEGREES F- SECTION 508.1.1 FBC M.
 508.1.1MAKEUP AIR TEMPERATURE. THE TEMPERATURE
 DIFFERENTIAL BETWEEN MAKEUP AIR AND THE AIR IN THE
 CONDITIONED SPACE SHALL NOT EXCEED 10?F (6?C) EXCEPT
 WHERE THE ADDED HEATING AND COOLING LOADS OF THE MAKEUP
 AIR DO NOT EXCEED THE CAPACITY OF THE HVAC SYSTEM.
  
 6) S1.0: PROVIDE COMPLETE ENGINEERING FOR INSTALLATION
 OF THE NEW RTU?S INCLUDING ATTACHING THE CURBS TO ROOF
 STRUCTURE, AND MOUNTING THE RTU?S ON THE CURBS- SECTION
 301.15 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  