| 2019-08-09 13:32:29 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19070090 |
| | 8/9/2019 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR THE |
| | KITCHEN HOOD, FIRE SUPPRESSION SYSTEM, AND WALK-IN |
| | COOLER AND FREEZER. PLEASE PLACE A NOTE ON THE PLAN. |
| | |
| | 2) M1.0: INDICATE HOW COMBUSTION AIR IS BEING PROVIDED |
| | TO THE NEW GAS COOKING APPLIANCES AND PROVIDE |
| | CALCULATIONS- SECTION 304.1 FBC-17 FUEL GAS. |
| | |
| | 3) M1.0: SUBMIT MANUFACTURER?S SPECIFICATIONS (CUT |
| | SHEETS) FOR THE NEW COOKING APPLIANCES- SECTION 623.1 |
| | FBC-17 FUEL GAS |
| | |
| | 4) M2.0: GRAVITY OR MOTORIZED SHUTOFF DAMPERS ARE |
| | REQUIRED FOR THE RTU O/A INTAKES - SECTION C403.2.4.3 |
| | FBC-17 ENERGY CONSERVATION. |
| | |
| | 5) M1.0: IT APPEARS THE O/A INTAKE FOR RTU-2 IS LOCATED |
| | WITHIN THE REQUIRED 10? CLEARANCE TO THE EXHAUST VENT- |
| | SEE SECTION 401.4 FBC M. |
| | |
| | 5) ADVISORY: THE HOOD IS UNDER SEPARATE PERMIT HOWEVER |
| | MEETING COMPLIANCE WITH SECTION 508.1.1 MAY REQUIRE |
| | CHANGES TO THE MAIN HVAC DESIGN. VERIFY THAT THE |
| | TEMPERATURE DIFFERENTIAL BETWEEN THE EXHAUST HOOD |
| | MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE DOES |
| | NOT EXCEED 10 DEGREES F- SECTION 508.1.1 FBC M. |
| | 508.1.1MAKEUP AIR TEMPERATURE. THE TEMPERATURE |
| | DIFFERENTIAL BETWEEN MAKEUP AIR AND THE AIR IN THE |
| | CONDITIONED SPACE SHALL NOT EXCEED 10?F (6?C) EXCEPT |
| | WHERE THE ADDED HEATING AND COOLING LOADS OF THE MAKEUP |
| | AIR DO NOT EXCEED THE CAPACITY OF THE HVAC SYSTEM. |
| | |
| | 6) S1.0: PROVIDE COMPLETE ENGINEERING FOR INSTALLATION |
| | OF THE NEW RTU?S INCLUDING ATTACHING THE CURBS TO ROOF |
| | STRUCTURE, AND MOUNTING THE RTU?S ON THE CURBS- SECTION |
| | 301.15 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |