2019-08-05 11:38:13GAS 1ST REVIEW**DENIED**PERMIT # 19070090
 1-SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE,
 TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING
 DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL GAS SECS.
 502 THRU 505
  
 2- SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 GAS
 APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC SEC.305.
  
 3) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES. WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR. 2017 FBC-FUEL
 GAS SEC.304.9.3
  
 4) YOU CALL OUT CSST ON SHT. P3 BUT DID NOT PROVIDE A
 SIZING TABLE FOR IT. SUBMIT TWO COPIES OF THE
 APPLICABLE SIZING TABLES USED TO SIZE THE GAS SYSTEM OR
 PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH
 SIZING TABLE(S) FROM THE GAS CODE OR OTHER STANDARD
 THAT WERE USED IN THE DESIGN OF THIS GAS SYSTEM. REFER
 TO THE 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND
 TABLES 402.4 (1) THRU 402.4 (37).
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  