| 2019-07-29 14:42:25 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19070090 |
| | ADD: 5335 N. MILITARY TRL. SUITE: 49 |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: ???????? |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JULY 29, 2019 |
| | ACTION: DENIED |
| | |
| | 1) THE DEMO FLOOR PLAN AND THE SHEET A1.0 ARCHITECTURAL |
| | FLOOR PLAN SHOW ONE WINDOW PAIN AND EGRESS DOOR |
| | SWAPPING PLACES. THE 2017 WEST PALM BEACH AMENDMENTS TO |
| | THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE |
| | CODE SECTION 104.9.1 USED MATERIALS AND EQUIPMENT. THE |
| | USE OF USED, RECYCLED, OR RECLAIMED MATERIALS WHICH |
| | MEET THE REQUIREMENTS OF THIS CODE FOR NEW MATERIALS IS |
| | PERMITTED. THE MATERIALS AND EQUIPMENT SHALL NOT BE |
| | REUSED UNLESS APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | I HAVE SPOKEN WITH THE BUILDING OFFICIAL ROBERT BROWN |
| | ABOUT THE REUSE OF THE DOOR, FRAME AND GLAZING FOR BOTH |
| | THE DOOR AND SIDE LIGHT. THE BUILDING OFFICIAL IS OK |
| | WITH THE REUSE OF THE PRODUCT AS LONG AS YOU CAN |
| | PROVIDE DOCUMENTATION THAT THE PRODUCT (DOOR & WINDOW |
| | STOREFRONT SYSTEM) WILL MEET TODAY CODE (WIND LOADS) |
| | AND PROVIDE INSTALLATION INSTRUCTIONS FOR THE POSITIVE |
| | AND NEGATIVE PRESSURES THAT WILL OCCUR ON THE |
| | STOREFRONT, FRAMING MEMBERS, GLAZING AND PROVIDE AN |
| | ANCHORING OF SAID SYSTEMS MEETING TODAYS WIND LOADS. |
| | |
| | 2) NEW ROOF TOP RTU AND CURB. THE MECHANICAL SHEET M2 |
| | REFERS TO THE ARCHITECTURAL SHEETS FOR THE CURB |
| | MOUNTING DETAILS. THE S1.0 SHEET DOES SHOW HOW TO |
| | RE-INFORCE THE BAR JOIST AND METAL ROOF DECK BUT THE |
| | PLAN IS SILENT OF THE ATTACHMENT OF THE RTU CURB TO THE |
| | ROOF FRAMING MEMBERS NOR THE RTU UNIT TO THE CURB. |
| | |
| | LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP |
| | EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS, |
| | DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL |
| | AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. |
| | |
| | 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| | LOADS. |
| | |
| | 3) 2017 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE |
| | CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | CURBS, INTAKE AND EXHAUST FANS AND VENTILATORS |
| | |
| | 4) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 5) THE FLOOR PLAN DOES NOT SHOW ANY INDOOR OR OUTDOOR |
| | SEASONAL SEATING. |
| | 5A ) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE |
| | CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE |
| | SEATING SPACES AND STANDING SPACES AT THE DINING |
| | SURFACES SHALL COMPLY WITH 902. |
| | |
| | 5B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES |
| | REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED |
| | THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING |
| | SURFACES AND WORK SURFACES. |
| | |
| | 5C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN |
| | RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL |
| | BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR |
| | SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS. |
| | |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |