| 2019-07-08 15:27:13 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE IS INSUFFICIENT INFORMATION SUBMITTED TO |
| | DETERMINE COMPLAINCE WITH THE FLORIDA FIRE PREVETNION |
| | CODE. |
| | |
| | PLEASE PROVIDE A DETAILED REVIEW OF WHAT THIS |
| | EDUCATIONAL OCCUPONACY IS, DIMENSION OF ALL |
| | ROOMS/SPACES, TOTAL SQUARE FOOTAGE.HOURS OF OPERATION, |
| | NUMBER OF STUDENTS, AGE OF STUDENTS, ETC. |
| | |
| | |
| | |
| | |
| | 2) THERE IS NO INDICATION OF COMPLINACE WITH ANY FIRE |
| | CODE. |
| | |
| | PROPOSED PROJECTS SHALL MEET THE REQUIREMENTS OF THE |
| | 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH |
| | INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101, |
| | INCLUDING CHAPTE 14, NEW EDUCATIONAL OCCUPANCIES |
| | |
| | PLEASE REVIEW AND ENSURE COMPLIANCE |
| | |
| | |
| | |
| | 3) THERE IS NO INDICATION OF A LIFE SAFETY PLAN. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND |
| | SPECIFICATIONS TO ENSURE COMPLIANCE WITH APPLICABLE |
| | CODES AND |
| | STANDARDS. |
| | |
| | PLEASE PROVIDE A DETAILED LIFE SAFETY PLAN |
| | |
| | |
| | |
| | |
| | 4) THERE APPEARS TO ONE FIRE ALARM DEVICE. |
| | |
| | PER NFPA 101, CH. 14, NEW EDUCATIONAL OCCUPANCIES. |
| | |
| | 14.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| | 14.3.4.1 GENERAL. |
| | 14.3.4.1.1 EDUCATIONAL OCCUPANCIES SHALL BE PROVIDED |
| | WITH A FIRE |
| | ALARM SYSTEM IN ACCORDANCE WITH SECTION 9.6. |
| | |
| | PLEASE PROVIDE FOR THE APPLICABLE FIRE ALARM SYSTEM AND |
| | A NOTE OF INTENT TO PROVIDE THE FIRE ALARM SYSTEM PER |
| | THE APPLICABLE CODE. |
| | |
| | ANY WORK ON A FIRE ALARM SYSTEM SHALL BE DONE UNDER |
| | SEPARATE PERMIT AND SHOP DRAWINGS. |
| | |
| | |
| | |
| | 5) THERE IS NO INDICATIONS OF A FIRE SPRINKLER SYSTEM. |
| | |
| | PER NFPA 101, CH. 14, NEW EDUCATIONAL OCCUPANCIES. |
| | |
| | 14.3.5 EXTINGUISHMENT REQUIREMENTS. |
| | 14.3.5.1* EDUCATIONAL OCCUPANCY BUILDINGS EXCEEDING |
| | 12,000 FT2 |
| | (1120 M2) SHALL BE PROTECTED THROUGHOUT BY AN APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH SECTION |
| | 9.7. |
| | |
| | PLEASE PROVIDE APPLICABLE INFORMATION TO DETERMINE IF A |
| | FIRE SPRINKLER SYSTEM IS REQUIRED. |
| | |
| | |
| | |
| | 6) THERE ARE NO INDICATIONS OF DOOR HARDWARE. |
| | |
| | PLEASE REVIEW NFPA 101 CH 14 AND PROVIDE APPLICABLE |
| | DOOR INFORMATION, HARDWARE AND LOCKING DEVICES PER THE |
| | CODE. |
| | |
| | 14.2.2.2 DOORS. |
| | 14.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| | PERMITTED. |
| | 14.2.2.2.2 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM |
| | AN AREA |
| | HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE |
| | PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK ONLY IF |
| | THE LATCH OR |
| | LOCK IS PANIC HARDWARE OR FIRE EXIT HARDWARE COMPLYING |
| | WITH |
| | 7.2.1.7. |
| | |
| | |
| | |
| | |
| | 7) THERE IS AN INDICATION OF A "SPACE OWNED BY OTHERS" |
| | THAT HAS A DOOR TO THIS PROPOSED OCCUPANCY. |
| | |
| | WHAT IS THE PURPOSE/OCCUPANCY TYPE OF THAT SPACE? |
| | |
| | THE OCCUPANCY IS REQUIRED TO BE SEPARATED BY A FIRE |
| | RATING PER NFPA 101, CH 6 OCCUPANCY CLASSIFICATION. |
| | |
| | 6.1.14 MULTIPLE OCCUPANCIES. |
| | 6.1.14.1 GENERAL. |
| | 6.1.14.1.1 MULTIPLE OCCUPANCIES SHALL COMPLY WITH THE |
| | REQUIREMENTS OF |
| | 6.1.14.1 AND ONE OF THE FOLLOWING: |
| | (1) MIXED OCCUPANCIES ? 6.1.14.3 |
| | (2) SEPARATED OCCUPANCIES ? 6.1.14.4 |
| | |
| | 6.1.14.1.2 WHERE EXIT ACCESS FROM AN OCCUPANCY |
| | TRAVERSES ANOTHER |
| | OCCUPANCY, THE MULTIPLE OCCUPANCY SHALL BE TREATED AS A |
| | MIXED |
| | OCCUPANCY. |
| | |
| | 6.1.14.3 MIXED OCCUPANCIES. |
| | 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE |
| | CLASSIFIED AS TO ITS USE IN |
| | ACCORDANCE WITH SECTION 6.1. |
| | 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST |
| | RESTRICTIVE |
| | REQUIREMENTS OF THE OCCUPANCIES INVOLVED, UNLESS |
| | SEPARATE SAFEGUARDS |
| | ARE APPROVED. |
| | 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.) |
| | 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED, |
| | EACH PART OF THE |
| | BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED |
| | IN THIS CHAPTER, |
| | SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY |
| | FIRE-RESISTIVE |
| | ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3, |
| | TABLE 6.1.14.4.1(A), |
| | AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED |
| | BY APPROVED |
| | EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY |
| | 6.1.14.4.6. |
| | |
| | PLEASE PROVIDE DETAILS AND THE REQUIRED SEPARATION. |
| | |
| | |
| | |
| | |
| | 8) THERE IS NO INDICATION OF THE ROOM/SPACES FLOOR, |
| | WALL AND CEILING FINISHES |
| | |
| | 14.3.3 INTERIOR FINISH. |
| | 14.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 10.2. |
| | 14.3.3.2* INTERIOR WALL AND CEILING FINISH. INTERIOR |
| | WALL AND |
| | CEILING FINISH MATERIALS COMPLYING WITH SECTION 10.2 |
| | SHALL BE |
| | PERMITTED AS FOLLOWS: |
| | (1) EXITS ? CLASS A |
| | (2) OTHER THAN EXITS ? CLASS A OR CLASS B |
| | (3) LOW-HEIGHT PARTITIONS NOT EXCEEDING 60 IN. (1525 |
| | MM) AND |
| | USED IN LOCATIONS OTHER THAN EXITS ? CLASS A, CLASS B, |
| | OR |
| | CLASS C |
| | 14.3.3.3 INTERIOR FLOOR FINISH. |
| | 14.3.3.3.1 INTERIOR FLOOR FINISH SHALL COMPLY WITH |
| | SECTION 10.2. |
| | 14.3.3.3.2 INTERIOR FLOOR FINISH IN EXIT ENCLOSURES AND |
| | EXIT ACCESS |
| | CORRIDORS AND SPACES NOT SEPARATED FROM THEM BY WALLS |
| | COMPLYING |
| | WITH 14.3.6 SHALL BE NOT LESS THAN CLASS II. |
| | 14.3.3.3.3 INTERIOR FLOOR FINISH SHALL COMPLY WITH |
| | 10.2.7.1 OR |
| | 10.2.7.2, AS APPLICABLE. |
| | |
| | PLEASE PROIVDE DETAILS INDICATING COMPLIANCE |
| | |
| | |
| | |
| | |
| | 9) THERE ARE EXIT SIGNS INDICATED BY THEY DO NOT |
| | INDICATE TYPE. |
| | |
| | PER NFPA 101, CH 14 |
| | |
| | 14.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS |
| | SHALL |
| | BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8. |
| | 14.2.9 EMERGENCY LIGHTING. EMERGENCY LIGHTING SHALL BE |
| | PROVIDED IN ACCORDANCE WITH SECTION 7.9. |
| | 14.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS |
| | SHALL |
| | HAVE SIGNS IN ACCORDANCE WITH SECTION 7.10. |
| | |
| | PLEASE PROVIDE DETAILS INDICATING COMPLIANCE WITH THE |
| | ABOVE. |
| | |
| | |
| | 11) THERE IS STORAGE INDICATED IN A CENTER/MAIN AREA. |
| | |
| | EXITS CAN NOT PASS THROUGH A HIGHER HAZARD AREA. |
| | |
| | PER NFPA 101 CH 7, MEANS OF EGRESS |
| | |
| | 7.5.1.6 EXIT ACCESS FROM ROOMS OR SPACES SHALL BE |
| | PERMITTED TO BE |
| | THROUGH ADJOINING OR INTERVENING ROOMS OR AREAS, |
| | PROVIDED THAT SUCH |
| | ROOMS OR AREAS ARE ACCESSORY TO THE AREA SERVED. |
| | FOYERS, LOBBIES, AND |
| | RECEPTION ROOMS CONSTRUCTED AS REQUIRED FOR CORRIDORS |
| | SHALL NOT BE |
| | CONSTRUED AS INTERVENING ROOMS. EXIT ACCESS SHALL BE |
| | ARRANGED SO |
| | THAT IT IS NOT NECESSARY TO PASS THROUGH ANY AREA |
| | IDENTIFIED UNDER |
| | PROTECTION FROM HAZARDS IN CHAPTERS 11 THROUGH 43. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 12) THERE DOES NOT APPEAR TO BE CODE COMPLIANT EXITS. |
| | |
| | PER NFPA 101, CH 7 MEANS OF EGRESS |
| | |
| | 14.2.4 NUMBER OF MEANS OF EGRESS. |
| | 14.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL BE IN |
| | ACCORDANCE |
| | WITH SECTION 7.4. |
| | 14.2.4.2 NOT LESS THAN TWO SEPARATE EXITS SHALL BE IN |
| | ACCORDANCE |
| | WITH THE FOLLOWING CRITERIA: |
| | (1) THEY SHALL BE PROVIDED ON EVERY STORY. |
| | (2) THEY SHALL BE ACCESSIBLE FROM EVERY PART OF EVERY |
| | STORY AND |
| | MEZZANINE; HOWEVER, EXIT ACCESS TRAVEL SHALL BE |
| | PERMITTED TO |
| | BE COMMON FOR THE DISTANCE PERMITTED AS COMMON PATH OF |
| | TRAVEL BY 14.2.5.3. |
| | 14.2.5 ARRANGEMENT OF MEANS OF EGRESS. SEE ALSO SECTION |
| | 7.5. |
| | 14.2.5.1 MEANS OF EGRESS SHALL BE ARRANGED IN |
| | ACCORDANCE WITH |
| | SECTION 7.5. |
| | 14.2.5.4 EVERY ROOM OR SPACE LARGER THAN 1000 FT2 (93 |
| | M2) OR WITH |
| | AN OCCUPANT LOAD OF MORE THAN 50 PERSONS SHALL COMPLY |
| | WITH THE |
| | FOLLOWING: |
| | (1) THE ROOM OR SPACE SHALL HAVE A MINIMUM OF TWO EXIT |
| | ACCESS |
| | DOORS. |
| | (2) THE DOORS REQUIRED BY 14.2.5.4(1) SHALL PROVIDE |
| | ACCESS TO |
| | SEPARATE EXITS. |
| | (3) THE DOORS REQUIRED BY 14.2.5.4(1) SHALL BE |
| | PERMITTED TO OPEN |
| | ONTO A COMMON CORRIDOR, PROVIDED THAT SUCH CORRIDOR |
| | LEADS TO |
| | SEPARATE EXITS LOCATED IN OPPOSITE DIRECTIONS. |
| | |
| | |
| | |
| | |
| | |
| | |
| | 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |