| 2019-09-20 10:22:46 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 4TH REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. MULTIPLE SETS OF DOCUMENTS FOR WINDOWS IN SUBMITTAL. |
| | REMOVE ANY DOCUMENTS THAT DO NOT APPLY TO THIS SCOPE OF |
| | WORK. |
| | |
| | 2. SITE SPECIFIC EVALUATION OF STORM PANELS BY J.W. |
| | KNEZEVCH, P.E. REQUIRES ORIGINAL SIGNATURE AND SEAL. |
| | DIGITAL COPIES ARE NOT ACCEPTABLE. |
| | FBC 107.1 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT, |
| | INTERIOR DESIGNER, LANDSCAPE ARCHITECT, OR ENGINEER |
| | LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE |
| | REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR |
| | DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA |
| | STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED |
| | FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR |
| | ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA |
| | STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| | OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE. |
| | |
| | 3. DESIGN CALC'S BY ENGINEERING EXPRESS REQUIRES |
| | ORIGINAL SIGNATURE AND SEAL OF DESIGNER FRANK L. |
| | BENNARDO, P.E. |
| | FBC 107.1 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT, |
| | INTERIOR DESIGNER, LANDSCAPE ARCHITECT, OR ENGINEER |
| | LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE |
| | REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR |
| | DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA |
| | STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED |
| | FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR |
| | ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA |
| | STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| | OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE. |
| | |
| | 4. COMMENT #3 FROM 3RD REVIEW HAS NOT BEEN ADDRESSED. |
| | PROVIDE INSTALLATION INSTRUCTIONS SWD014 FOR THE |
| | STRUCTURAL BEAM MULLIONS. |
| | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE WINDOW MULLION SUBMITTALS. |
| | |
| | ADVISORY: |
| | |
| | 4X FEES |
| | |
| | F.S. 553.80 (2) (B) |
| | (B)?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | |
| | |