| 2019-08-23 14:54:22 | 1ST REVIEW: 19070081 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1.SHOW HEIGHT OF BREAKROOM SINK SHALL BE MAX 34"SHT |
| | A400 DETAIL #8. PER FBC ACC 606.2-3 |
| | |
| | 2. SHT. A401 ADDRESS THE FOLLOWING COMMENTS. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | A)GRAB BARS SHALL BE MEASURED TO THE TOP OF THE |
| | GRIPPING SURFACE FROM FINISHED FLOOR. PER FBC ACC 609.4 |
| | B)TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| | DISPENSER. PER FBC ACC 604.7 |
| | C) PROVIDE DIMENSIONS ON THE CLEAR FLOOR SPACE ON THE |
| | TOILET AND LAVATORY. FBC ACC 604.3.1 ,606.2 |
| | D) THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES |
| | MINIMUM ON THE OTHER SIDE.FBC ACC 604.5.2 |
| | E) THE HIGH SPOUT ON THE WATER FOUNTAIN SHALL BE 38 MIN |
| | FBC ACC 602.7 |
| | |
| | 3.SHT. P003 P101 THE FLOOR DRAIN UNDER THE OUTSIDE PREP |
| | TABLE IS NOT VENTED IT SHALL BE VENTED BEFORE IT |
| | CONNECTS TO THE BUILDING DRAIN. PER FBC PL 1002.4 |
| | |
| | 5. HOW DOES THE PUBLIC HAVE ACCESS TO THE WATER |
| | FOUNTAIN IT APPEARS THEY WOULD HAVE TO TRAVEL THROUGH A |
| | WORK AREA. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 6. PROVIDE MANUFACTURE SPECIFICATIONS FOR THE |
| | FOLLOWING. |
| | A) BOOSTER PUMP. |
| | B) ASPIRATOR. |
| | C) ALL BACKFLOW DEVICES THEY SHALL BE LEAD FREE. |
| | |
| | 7. SHOW ACCESSIBILITY FOR THE SHOWER PER FBC ACC |
| | 608.2.1 / 608.3.1 / 608.4 / 608.5.1 / 608.6 / 609.4 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |