| 2019-08-13 17:17:19 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19070067 |
| | 8/13/2019 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | 1) SHEET M2.17: PROVIDE SYSTEM SIZING CALCULATIONS FOR |
| | THE AHU-CH- SECTION 312.1 FBC M. |
| | 2) M2.17: NORMAL AND EMERGENCY VENTILATION SHALL BE |
| | PROVIDED FOR THE CHILLER ROOM- SEE SECTIONS 1105.6 & |
| | 1105.6.3 FBC M. PLEASE INDICATE HOW THE VENTILATION |
| | SYSTEM DESIGN AS SHOWN ON THE PLAN WILL MEET COMPLIANCE |
| | FOR BOTH NORMAL AND EMERGENCY VENTILATION. PROVIDE |
| | CALCULATIONS AND THE SEQUENCES OF OPERATION ON THE |
| | PLAN. |
| | 3) M2.17: SUBMIT MANUFACTURER?S SPECIFICATIONS AND |
| | INSTALLATION INSTRUCTIONS FOR THE REFRIGERANT DETECTOR |
| | WITH APPROVAL STAMP BY THE ENGINEER OF RECORD. PLEASE |
| | NOTE THIS MAY BE A DEFERRED SUBMITTAL AS NOTED BELOW. |
| | 4) M22.17: DEFERRED SUBMITTALS: THE MIAMI-DADE NOA?S |
| | FOR THE AC STAND, LOUVERS, AND THE SPECS FOR THE |
| | REFRIGERANT DETECTOR MAY BE SUBMITTED WITH THE PLANS |
| | BEARING APPROVAL STAMPS BY THE EOR, OR MAY BE DEFERRED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |