Notes
Date Text
2019-07-11 13:27:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 30A
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMEMTS: DENIED
  
 COMMENTS REQUIRING ARCHITECTURAL RESPONSE:
 SATISFACTORY RESPONSE TO ARCHITECTURAL COMMENTS ARE
 REQUIRED FOR PLUMBING APPROVAL TO COMPLY WITH THE
 REQUIREMENTS OF FBC PL 404.
  
 1. PLAN SHEET A-0.1: WPB FBC HAS ADOPTED FBC
 ACCESSIBILITY, 6TH EDITION 2017. PER WPB FBC 107.2.1,
 CHANGE BUILDING CODE SUMMARY TO REFLECT THE SAME.
 2. BREAK AREA SINK: PLAN SHEET A-2.1 INDICATES A 30? X
 48? CLEAR FLOOR SPACE FRONT APPROACH TO THE SINK THAT
 TERMINATES AT THE FRONT OF THE CABINET AND PLAN SHEET
 A-3.1 PROVIDES NOTE FOR OPTIONAL DOORS WITH INTEGRAL
 TOEKICK TO PROVIDE FRONT APPROACH ACCESSIBILITY
 CLEARANCE.
 A. PER WPB FBC 107.2.1, PROVIDE THE FOLLOWING:
 1) DELETE REFERENCE TO OPTIONAL
 2) INDICATE ON THE PLAN VIEW (PLAN SHEET A-2.1), THE
 CLEAR FLOOR DIMENSIONED SPACE FOR THE FRONT APPROACH TO
 THE SINK COMPLYING WITH FBC ACC 306.
 3) PROVIDE A SIDE VIEW ELEVATION ON PLAN SHEET A-3.1 OF
 SINK SECTION SHOWING KNEE AND TOE CLEARANCE FOR THE
 SINK COMPLYING WITH FBC ACC 306.
 3. ELECTRIC WATER COOLER: PER WPB FBC 107.2.1, PROVIDE
 A SIDE AND FRONT VIEW ELEVATION ON PLAN SHEET A-3.1 OF
 BI-LEVEL WATER COOLER SHOWING SPOUT HEIGHT AND LOCATION
 PER FBC 602.4, 602.5 AS WELL AS KNEE AND TOE CLEARANCE
 FOR THE SINK COMPLYING WITH FBC ACC 306.
 4. PLAN SHEET A-3.1 DETAIL 2
 A. CENTERLINE OF WATER CLOSET TO SIDE WALL SHALL BE 16?
 MIN/18? MAX PER FBC ACC 604.2. THIS REQUIREMENT IS
 NOTED ON PLAN SHEET TI-2.2 BUT IS LUMPED IN WITH
 NUMEROUS OTHER DETAILS MAKING IT DIFFICULT FOR USERS.
 PER WPB FBC 107.2.1, PLACE THIS INFORMATION ON PLAN
 SHEET A-3.1 DETAIL 2.
 B. REAR WALL GRAB BAR SHALL BE 12? FROM CENTERLINE OF
 WATER CLOSET TOWARD SIDE WALL AND 24? MINIMUM
 CENTERLINE OF WATER CLOSET TO THE OTHER SIDE. THIS
 REQUIREMENT IS NOTED ON PLAN SHEET TI-2.2 BUT IS LUMPED
 IN WITH NUMEROUS OTHER DETAILS MAKING IT DIFFICULT FOR
 USERS. PER WPB FBC 107.2.1, PLACE THIS INFORMATION ON
 PLAN SHEET A-3.1 DETAIL 2.
  
  
 COMMENTS REQUIRING PE RESPONSE
  
 1. PLAN SHEET P-1: FIXTURE SCHEDULE
 A. LAV
 1)PER FBC PL 416.5, PROVIDE TEMPERED WATER DELIVERED
 FROM LAVATORIES AND GROUP WASH FIXTURES LOCATED IN
 PUBLIC TOILET FACILITIES PROVIDED FOR CUSTOMERS,
 PATRONS AND VISITORS. TEMPERED WATER SHALL BE DELIVERED
 THROUGH AN APPROVED WATER-TEMPERATURE LIMITING DEVICE
 THAT CONFORMS TO ASSE 1070 OR CSA B125.3.
 2)PER WPB FBC 107.2.1, PROVIDE AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
 B. EWC
 1) PER WPB FBC 107.2.1 PROVIDE SPECIFICATION SHEET FORE
 OWNER SUPPLIED BILEVEL WATER COOLER SHOWING ADA
 COMPLIANCE. PER WPB FBC 107.3.4.1, THIS MAY BE PROVIDED
 AS A DEFERRED SUBMITTAL. ***SEE 107.3.4.1 DEFERRED
 SUBMITTALS BELOW
 A. SINK
 1)PER WPB FBC 107.2.1 PROVIDE SPECIFICATION SHEET FORE
 OWNER SUPPLIED SINK AND FAUCET SHOWING ADA COMPLIANCE.
 PER WPB FBC 107.3.4.1, THIS MAY BE PROVIDED AS A
 DEFERRED SUBMITTAL. ***SEE 107.3.4.1 DEFERRED
 SUBMITTALS BELOW
  
 *** 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY
 SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE
 BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED
 AND FOUND TO BE IN GENERAL CONFORMANCE TO THE DESIGN OF
 THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  