| 2019-07-12 14:33:46 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET A 02 - DOOR D 4 IS INDICATED OPENING INTO THE |
| | EXIT CORRIDOR OBSTRUCTING THE REQUIRED EGRESS WIDTH. |
| | |
| | PER NFPA 101, CH 7, MEANS OF EGRESS |
| | |
| | 7.2.1.4.3 DOOR LEAF ENCROACHMENT |
| | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE |
| | REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, |
| | OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT |
| | MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A |
| | CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN, |
| | UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| | EXISTING BUILDING. |
| | (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS |
| | PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED |
| | WIDTH OF THE STAIR LANDING WHEN THE DOOR |
| | LEAF IS FULLY OPEN. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | |
| | 2) SHEET A 02 - THERE ARE NO INDICATIONS OF FIRE |
| | SPRINKLERS WITHIN THIS SUITE. |
| | |
| | PLEASE CONFIRM. |
| | |
| | ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE DONE |
| | UNDER SEPARATE PERMIT AND SHOP DRAWINGS. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT |
| | |
| | |
| | |
| | |
| | 3) SHEET E 1 - THERE ARE INDICATIONS OF FIRE ALARM |
| | EQUIPMENT/DEVICES. |
| | |
| | ALL FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE PERMIT |
| | AND SHOP DRAWINGS. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT |
| | |
| | |
| | |
| | |
| | 4) ELECTRICAL SHEETS - INFORMATION: ANY ACCESS CONTROL |
| | EQUIPMENT/DEVICES SHALL BE INSTALLED UNDER SEPARATE |
| | PERMIT AND SHOP DRAWINGS. |
| | |
| | PLEASE ENSURE SEPARATE SUBMITTAL IF APPLICABLE. |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |