Plan Review Notes
Plan Review Notes For Permit 19070048
Permit Number 19070048
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-07-12 14:33:46THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 02 - DOOR D 4 IS INDICATED OPENING INTO THE
 EXIT CORRIDOR OBSTRUCTING THE REQUIRED EGRESS WIDTH.
  
 PER NFPA 101, CH 7, MEANS OF EGRESS
  
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR
 LEAF IS FULLY OPEN.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 2) SHEET A 02 - THERE ARE NO INDICATIONS OF FIRE
 SPRINKLERS WITHIN THIS SUITE.
  
 PLEASE CONFIRM.
  
 ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE DONE
 UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT
  
  
  
  
 3) SHEET E 1 - THERE ARE INDICATIONS OF FIRE ALARM
 EQUIPMENT/DEVICES.
  
 ALL FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT
  
  
  
  
 4) ELECTRICAL SHEETS - INFORMATION: ANY ACCESS CONTROL
 EQUIPMENT/DEVICES SHALL BE INSTALLED UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS.
  
 PLEASE ENSURE SEPARATE SUBMITTAL IF APPLICABLE.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  