Plan Review Notes
Plan Review Notes For Permit 19070042
Permit Number 19070042
Review Stop P
Sequence Number 1
Notes
Date Text
2019-07-18 17:05:27CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 96= STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMEMTS: DENIED
 1. A COMPLETE REVIEW COULD NOT BE DONE AT THIS TIME.
 2. PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES (840 MM) MINIMUM AND 36
 INCHES (915 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE, NOT TO THE CENTER.
 3. PER 604.8.1.2, DOORS SHALL BE LOCATED IN THE FRONT
 PARTITION OR IN THE SIDE WALL OR PARTITION FARTHEST
 FROM THE WATER CLOSET. WHERE LOCATED IN THE FRONT
 PARTITION, THE DOOR OPENING SHALL BE 4 INCHES (100 MM)
 MAXIMUM FROM THE SIDE WALL OR PARTITION FARTHEST FROM
 THE WATER CLOSET. WHERE LOCATED IN THE SIDE WALL OR
 PARTITION, THE DOOR OPENING SHALL BE 4 INCHES (100 MM)
 MAXIMUM FROM THE FRONT PARTITION. DOOR FOR THE TOILET
 ROOM ADJACENT TO JANITOR CLOSET IS NOT COMPLIANT.
 4. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE THE
 FOLLOWING:
 A. FLOOR PLAN SHOWING SANITARY AND WATER DISTRIBUTION;
 SHOW POINTS OF CONNECTION TO EXISTING WATER SERVICE AND
 SEWER
 B. SHOW LOCATION OF EXISTING BACKFLOW PREVENTER OR
 PROVIDE NEW.
 C. WATER RISER DIAGRAM
 D. WATER HEATER SCHEDULE AND DETAIL SHOWING COMPLIANCE
 WITH FBC PL CHAPTER 5.
 E. FIXTURE SCHEDULE
 F. THERMAL MIXING VALVES FOR LAVATORIES
 5. REGARDING SANITARY PLUMBING RISER ON E101:
 A. PLACE ON DEDICATED PLUMBING PAGE (S) WITH OTHER
 REQUIRED INFORMATION AND SHALL MATCH THE FLOOR PLAN.
 B. MOP SINK SHALL BE INDIVIDUALLY VENTED PER FBC PL
 910.1. THE FUTURE SINK VENT DOES NOT PROVIDE A VENT FOR
 THE MOP SINK UNDER SECTION 911 OR 912.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19070042 2921 N AUSTRALIAN AVE
  